ID50 Series Panel - Installation, Commissioning & Configuration Manual
997-263, Issue 4
September 2002
Fuses:
The location of the panel fuses is given here, together with their
ratings and their type.
a. MF1
Mains Supply
b. FS1
Transformer
c. FS2
Battery
T = time delay (i.e. anti-surge), H = high break capacity, as
defined by EN 60127.
Outputs:
a. Two dedicated Sounder Outputs.
b. Two Sounder or Volt-free Contact (VFC) - selectable
outputs.
c. Two -VE Outputs (RLY) - unselectable outputs.
d. One loop output.
e. One DC auxiliary output.
Sounder Output Rating
Type:
Output voltage:
Maximum load:
Fuse rating:
Monitoring:
Volt-free Contact (VFC) Output Rating
Type:
Maximum load:
Fuse rating:
Switched -VE Output Rating
Output voltage:
Maximum load:
Loop Output
Output voltage:
Maximum load:
Max. loop impedance:
Max. loop capacitance: 0.5mF
Up to 198 loop devices (up to 99 sensors and 99 modules) may
be fitted to the analogue loop.
The communication with devices on the loop uses the Notifier
‘CLIP’ protocol. Refer to Hardware Recommendations for a
list of compatible devices and loading limitations.
A1 - 4
T 2A 250V H
T 5A 250V H
T 5A 250V H
Voltage reversal.
26
to
28V
when
-6.8V to -9V when inactive.
1A Total (max. 700mA per output).
Not applicable.
Open- and short-circuit.
Single-pole change-over
Contacts rated 30V 1A
Not applicable
21 to 30V
83mA (total for both outputs)
22.5 to 26.4V.
0.5A peak current*
20 ohms (-ve cable only, with
duplicate address detection) or
40 ohms (-ve cable only, without
duplicate address detection).