ID50 Series Panel - Installation, Commissioning & Configuration Manual
CAUTION-
ENERGY HAZARD!
NEVER short the battery
terminals
2
TB2 (0 V)
TB2 (BAT +)
Battery 1
4
Battery
Battery
1
2
5
997-263, Issue 4
September 2002
4.5.2 Batteries
The ID50 Series Panel back box holds up to two 12V,
12Ah batteries. the batteries are not supplied with the
panel. A valve-regulated, lead-acid type MUST be used.
To connect the batteries:
1 Externally isolate the mains supply at the third-party-
2 Connect the red wire from the terminal block, TB2
3 Turn on the AC mains supply and verify that after
Battery 2
4 Connect the interlink cable to the negative terminal
5 Reset the panel and check that the LCD displays the
Battery Disposal
As a minimum, replace the batteries every four years.
Always dispose of the batteries in accordance with the
battery manufacturer’s recommendations and local
regulations.
Status: NORMAL
supplied isolation unit, remove the cover and fit the
batteries in the back box. Connect the mains/battery/
supply wiring plug to the power socket, between the
mains fuse (FS1) on the left and the battery fuse (FS2)
to the right.
(BAT+) to the positive terminal of battery 2 and the
black wire from the terminal block, TB2 (0V) to the
negative terminal on battery 1.
Connect one end of the interlink cable to battery 1
positive terminal only.
DO NOT connect both ends of the interlink cable at
this stage.
power-up:
i
The panel indicates ‘CPU RESTART’.
ii The buzzer sounds.
iii The FAULT and SYSTEM FAULT LEDs illuminate.
on battery 2.
‘Status: NORMAL’ message and that the FAULT and
SYSTEM FAULT LEDs extinguish.