Notifier ID50 Installation, Commissioning & Configuration Manual page 52

Table of Contents

Advertisement

ID50 Series Panel - Installation, Commissioning & Configuration Manual
1
or
2
6
1
0
5
997-263, Issue 4
September 2002
5.5.15 Number of Repeaters
The Number of Repeaters menu allows the quantity of
repeaters connected to the RS485 Communications Link
to be entered. The panel displays a fault if this quantity
does not equal the number of repeaters connected. To
enter the number:
1 From the Commissioning menu, press the ‘
on the numeric keypad to enter the Setup menu.
[Setup] Language =
> : Change
8
2 Press the ‘
menu until the Number of Repeaters menu is
displayed.
[Setup]
> : Change
3 Press the ‘
repeaters to be entered.
[Setup]
Enter new value ____
4 Enter the required number using the numeric buttons;
for example if entering a value of 10, first press ‘1’,
then ‘0’.
[Setup]
Enter new value 1 0
5 Press the ‘
menu.
5.5.16 Transmission Device
The Transmission Device activates in response to an
alarm condition. The ‘Transmission Device’ menu enables
the configuration of either a continuous or a 6 second
pulse response. This feature is required for VdS-
compliant operation only.
5.5.17 FWP Input 4 Disabled
This menu disables either the Extinguishing System or
the Sounder Outputs. This feature is required for VdS-
compliant operation only.
46
English
× : More
/
’ buttons to step through the Setup
2
8
No. of Repeaters = 0
× : More
’ button to enable the number or
6
No. of Repeaters = 0
3
: Confirm
No. of Repeaters = 0
3
: Confirm
’ button to confirm the setup or press
5
’ repeatedly to cancel and return to the Setup
4
’ button
1
< : Exit
< : Exit
< : Cancel
< : Cancel