Notifier IFS-2600 Operation, Installation, And Maintenance Manual

Hide thumbs Also See for IFS-2600:

Advertisement

Quick Links

IFS-2600
Fire Indicator Panel
O
, I
&
PERATION
NSTALLATION
P
M
ROGRAMMING
ANUAL
1.02
19/04/2011
Rev:
DOC-01-009
ECN11-0012

Advertisement

Table of Contents
loading

Summary of Contents for Notifier IFS-2600

  • Page 1 IFS-2600 Fire Indicator Panel & PERATION NSTALLATION ROGRAMMING ANUAL 1.02 19/04/2011 Rev: DOC-01-009 ECN11-0012...
  • Page 2 Brief description of the content you think should be improved or corrected  Your suggestion for how to correct/improve documentation Send email messages to: techpubs@notifier.com.au Please note this email address is for documentation feedback only. If you have any technical issues, please contact your nearest branch for technical support.
  • Page 3: Installation Precautions

    Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power from the sides or rear. Before making can be connected to the fire alarm control modifications, verify that they will not interfere with panel.
  • Page 4: Table Of Contents

    - Installation ................16 4.1. Compatible Detectors .................16 4.2. Specification ....................17 4.3. Overview of IFS-2600 System Equipment ...........20 4.4. Power Supply .....................21 4.4.1 Power Supply Ratings & Settings for NI-2017-01 & NI-2025-01 Boards ..21 4.4.2. Power Supply Ratings & Settings for IFS-2005 & IFS-2006 Boards .... 23 4.4.3.
  • Page 5 IFS-2600 Fire Indicator Panel Section 1 About this Manual 5.4. Global Options & Programming..............46 5.5. Print Programming Data................48 Section 6 Appendix ................. 49 6.1. Appendix A ....................49 6.2. Appendix B ....................50 6.3. Appendix C....................52 6.4. Technical Drawings..................59 6.4.1. System Sensor Conventional Detector Connection Diagram ...... 59 6.4.2.
  • Page 6: Section 1 - About This Manual

    IFS-2600 Fire Indicator Panel Section 1 About this Manual Section 1 - About this Manual 1.1. Notes, Cautions and Warnings This manual contains notes, cautions and warnings to alert the reader as follows: NOTE: Supplement information for a topic such as tips and references.
  • Page 7: Section 2 - System Overview

    A serial printer can also be connected if required. The printer can be used to output programming information for ease of modification, for safekeeping and to assist in the commissioning of the installation. The IFS-2600 uses serial chain mimic outputs which significantly saves time and costs of cabling to mimic panels.
  • Page 8: System Description

    Door Holder Power Supply Transformer Table 2-1, IFS-2600 Panel Components IFS-2600 requires the basic equipment as listed above to function. The microprocessor and other sensitive electronic components are located on the Main Processor Board, located on the inner panel that can be easily removed during installation to allow improved terminal access.
  • Page 9: Lcd Display

    IFS-2600 Fire Indicator Panel Section 2 System Overview 2.5. LCD Display In addition to the LED's a 16-character x 2-line liquid crystal display is provided to indicate system status, changing events and programming information. Any keystroke or event will actuate the backlighting on the display for better readability in dark areas.
  • Page 10: Keypad

    IFS-2600 Fire Indicator Panel Section 2 System Overview 2.6. Keypad The custom-designed 30 key membrane keypad is the users interface to accessing all zone and global functions of the IFS-2600.These 30 keys consist of; FIRE FIGHTER’S FACILITY BELLS WARNING SYSTEM Figure 2-1, IFS-2600 Keypad Fire Fighter’s...
  • Page 11 IFS-2600 Fire Indicator Panel Section 2 System Overview Descriptor Colour Function Buzzer MAINS ON Green Illuminates when there is AC supply to the panel. Illuminates if the battery fails a battery test. BATTERY Yellow Illuminates if batteries are disconnected >30 seconds.
  • Page 12: Section 3 - Operation

    IFS-2600 Fire Indicator Panel Section 3 Operation Section 3 - Operation 3.1. Suggested Alarm Procedure The following is a suggested alarm procedure for use by building fire officers or duty wardens. The fire indicator panel is designed for use by qualified fire fighters and it is strongly recommended that the fire panel not be operated in an emergency situation by anyone other than suitably qualified fire fighters.
  • Page 13: Global Operator Functions

    IFS-2600 Fire Indicator Panel Section 3 Operation  ISOLATE ISOLATE The isolate function prevents the transmission of alarms or faults from the zones to the master alarm facility. The isolate key only operates on zones with acknowledged alarms. EXT BELL ...
  • Page 14 IFS-2600 Fire Indicator Panel Section 3 Operation For IFS-2005 & IFS-2006 Boards: This function tests the performance of the batteries fitted to the system. Pressing this button will initiate a battery test as specified in AS4428. The test will temporarily disconnect the batteries from the panel and apply load on the batteries for 15 seconds.
  • Page 15 IFS-2600 Fire Indicator Panel Section 3 Operation For the duration of walk test mode, all zones are changed to output configuration #2 (indicate and ring bells only) and all zones are set to type #1 (standard latching, 2 second). If the bells are not required to ring during walk test, simply press the "EXT BELL ISOLATE" key once. The EXT BELL ISOLATE LED will illuminate to verify that the bells have been isolated.
  • Page 16: Zone Operator Function

    LED’s on the respective selected zone(s) will start blinking with a continuous buzzer sound and a red LED light is illuminated next to BT INH location on PSI board. NOTE: This LED is for new IFS-2600 termination boards(NI-2025-01) only. Pressing ACK acknowledge key stops the buzzer sound and blinking LED automatically turns into continuous lighting.
  • Page 17 IFS-2600 Fire Indicator Panel Section 3 Operation  FAULT TEST ENTER FAULT TEST The fault test function momentarily disconnects the detection zone(s) under test and simulates the worst- case condition for fault. A resistor load equal to worst case fault is placed on the zone continuously for 5 seconds then the zone is returned back to its normal condition.
  • Page 18 IFS-2600 Fire Indicator Panel Section 3 Operation If a correct entry is made, the zone is immediately isolated. If the zone is already in alarm, all of its alarm outputs are isolated and indicators remain visible. If the "ALL" function is performed, all zones will be isolated, regardless of their previous state. Performing the "ALL"...
  • Page 19: Standard Outputs

    IFS-2600 Fire Indicator Panel Section 3 Operation 3.5. Standard Outputs Output Type Description Change Normally energised relay: Will de- energise if system volts fall below 21V. This Standby over relay usually means AC has failed and batteries are getting low. I.e. panel is about ...
  • Page 20: Relay Expansion Boards

    IFS-2600 Fire Indicator Panel Section 3 Operation 3.6. Relay Expansion Boards The maximum number of boards that can be fitted is eight (i.e.: 64 relays). Each board contains 8 change-over relay outputs. Relays can be programmed to simulate:  Brigade Alarm Relay #1 ...
  • Page 21: Section 4 - Installation

    IFS-2600 Fire Indicator Panel Section 4 Installation Section 4 - Installation 4.1. Compatible Detectors Make Model Type Model Number System Sensor Thermal Type A 5451AUS System Sensor Thermal Type A 51A51 System Sensor Thermal Type B 4451AUS System Sensor Thermal...
  • Page 22: Specification

    Approval No AFP-1553 C-Tick Approval No. N1336 Environmental Limits: -10 Deg.C to +55 Deg.C Dry heat. +40 Deg.C @ 93% Relative Humidity. Specification for IFS-2600 in CAB650/CAB900: Cabinet Zinc Sealed Steel 1.2mm, Powder Coated, Hinged Inner & Outer Door Outside Dimensions Refer to Figure 4-1 &...
  • Page 23 M205 1A Slow Blow Bell Fuse F7 M205 1A Warning System Fuse F8 M205 1A Fuse F9 M205 1A AZF Circuits Current Limited 40mA E.O.L Resistor on AZFs, 4K7 Ohms monitored outputs, Bells, Warning system, ACF Table 4-2, IFS-2600 Panel Configuration DOC-01-009...
  • Page 24 IFS-2600 Fire Indicator Panel Section 4 Installation CAB 650 Mechanical Dimensions: Figure 4-1, CAB650 Dimensions CAB 900 Mechanical Dimensions: Figure 4-2, CAB900 Dimensions DOC-01-009...
  • Page 25: Overview Of Ifs-2600 System Equipment

    IFS-2600 Fire Indicator Panel Section 4 Installation 4.3. Overview of IFS-2600 System Equipment 4 CORE CABLE TX, CTS, GND DB-9 FEM ALE SERIAL PRINTER OUTPUTS M AIN TERM INATION BOARD M AIN PROCESSOR BOARD PCB1125 NI-2025-01 CABLE C32 NI-2004-01 BELL/ACF...
  • Page 26: Power Supply

    Power Supply (Brick power supply – NPS-2/NPS-5/NPS-11): This type of power supply is used in new IFS-2600 panels in conjunction with NI-2025-01 and NI-2017-01 boards to provide external & internal power supply to the panel. (Refer to Section 4.4.1 for more details)
  • Page 27 IFS-2600 Fire Indicator Panel Section 4 Installation Power Supplies NPS-2, NPS-5, NPS-11 NPS-2 AC 100-240V; 50/60Hz; 1.3A AC Operational Voltage NPS-5 AC 100-240V; 50/60Hz; 2.5A NPS-11 AC 100-240V; 50/60Hz; 5A NPS-2 2.6 Amp Output Current @ 27.3V NPS-5 5.6 Amp...
  • Page 28: Power Supply Ratings & Settings For Ifs-2005 & Ifs-2006 Boards

    30 ohm, 5W resistor connected between the 24v Aux Output and the battery positive terminal. A 1N4004 Diode (Notifier part number #286) or similar should also be fitted in series with the resistor to stop the battery from pulling down the main panel voltage. Trickle charging the battery by this method may take several hours to bring it up to the minimum level.
  • Page 29 IFS-2005 and adjust the voltage on the external power supply until the voltage is 26.5V 0.5V (26.0V – 27.0V). Note: This voltage is not critical for the operation of the IFS-2600 panel, but the voltage must not go outside the limits as specified for the field ancillaries that it powers.
  • Page 30: Battery Type And Capacities

    1. A 6A4 or P600G rectifier diode (Notifier part number #266) is to be installed in series with the external +27V output of the IFS-2600 termination board.
  • Page 31: Technical Description

    Section 4 Installation 4.5. Technical Description General The IFS-2600 in its most basic form comprises of three boards, the main control board, the main termination board and the power supply board. The main control board contains the Microprocessor, EPROM, RAM and E ROM.
  • Page 32 + and - terminals of the detector base. The maximum number of detectors that can ® be installed on each AZF is dependent on the type of detector and is listed in the IFS-2600 ActivFire listing.
  • Page 33 IFS-2600 Fire Indicator Panel Section 4 Installation Manual Call Point (MCP) For IFS-2005 Boards: Panel MCP connection is achieved by wiring from the zone, to the MCP, to the MCP loop then out to the field with the EOL across the last detector. The MCP is the first device on the circuit and both fault and alarm conditions will be indicated.
  • Page 34 IFS-2600 MIMIC MIMIC Outputs: A mimic output is standard on all IFS-2600 panels. This output mimics the status of all alarm zones fitted on the panel to a remote mimic panel in the building. The four (4) wire serial mimic decoder board can be connected to the panel by using a 4-core cable. 4 conductors are used, 24VDC, 0V, data, &...
  • Page 35 IFS-2600 Fire Indicator Panel Section 4 Installation Programming By Computer Programming of the zones, relays, global functions and time can be set with the DOS based program “2600/SW” using the printer port (Cannot be used with Windows XP). After the cable is installed, the program can be run and the menu will prompt for the available functions.
  • Page 36 IFS-2600 Fire Indicator Panel Section 4 Installation Fault Threshold Comparator TP6 (For IFS-2005 & IFS-2006 Boards Only) With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER SUPPLY as above. Measure the voltage between system 0V and TP6. Adjust multi-turn potentiometer VR1, and adjust until the voltage is as per the following table.
  • Page 37 IFS-2600 Fire Indicator Panel Section 4 Installation IFS804 - JP1-7 Zone Board Addressing Jumper JP1 to JP7 on zone expansion board IFS-804 selects the addressing for the zones. Place jumper in link position for the appropriate 8 zones to which the expansion board applies...
  • Page 38: Placing Into Operation

    All operational zones adequately identified  All fuses correct value and fitted properly  All other modules securely fitted  AS 4428 Manufactured & Tested label affixed You are now ready to power up the IFS-2600 Fire Indicator Panel. DOC-01-009...
  • Page 39 IFS-2600 Fire Indicator Panel Section 4 Installation Power up Checklist  Ensure batteries are disconnected  Turn mains switch to "on"  The "mains on" LED should light  Allow 15 seconds for the panel to perform its start up tests ...
  • Page 40 Fault Record FAULT CORRECTION DATE TESTS SATISFACTORILY COMPLETED. TESTED BY _______________________________ SIGNATURE _______________________________ DATE OF TEST ____________________________ If all faults have been rectified and all tests are completed satisfactorily, the IFS-2600 fire indicator panel is now ready for operation. DOC-01-009...
  • Page 41: Section 5 - Programming

    ENTER Programming Mode The liquid crystal display will display all messages and prompts required to program the IFS-2600 Panel. Only the "PREVIOUS","NEXT","SELECT","EXIT" AND "ENTER" keys are used in programming mode. All other keys will give an error beep and should be ignored.
  • Page 42 IFS-2600 Fire Indicator Panel Section 5 Programming Relays TYPE MAPPING ISOLATE RELAY ANCILLARY OUTPUT (ACF) BRIGADE RELAY #1 BRIGADE RELAY #2 FAULT RELAY MAINS FAIL RELAY GENERAL ALARM RELAY BELL OUTPUT DOOR HOLDER RELAY MAP - AND (00)(00)(00)(00)(00) MAP - OR...
  • Page 43 IFS-2600 Fire Indicator Panel Section 5 Programming EXIT Programming Mode SAVE CHANGES (NO) Use the "NEXT" & "PREVIOUS" keys to scroll through "YES" & "NO". Once the desired option has been highlighted, pressing the "SELECT" button will select it. Highlighting "YES" and pressing "SELECT" will write all changes made to the system memory (E ROM) and the panel will then restart.
  • Page 44: Zone Options & Programming

    IFS-2600 Fire Indicator Panel Section 5 Programming 5.2. Zone Options & Programming 5.2.1. Zone Options Description of Alarm Zone Types Different zone types can be selected using the programming mode. Each zone can be selected as any one of the following:...
  • Page 45: Zone Programming

    IFS-2600 Fire Indicator Panel Section 5 Programming If an alarm is received, the detector is reset again and TIMER#2 is also reset. This monitoring continues until the 60-second timer (TIMER#1) has elapsed and then the NEXT alarm signal will trip the zone into "FULL ALARM". This is the stage at which all mapped relays, bells etc. will operate.
  • Page 46 IFS-2600 Fire Indicator Panel Section 5 Programming ZONE Type ZONE # ALL TYPE STD LATCHING Use the "NEXT" & "PREVIOUS" keys to scroll through STD LATCHING STD LATCHING AVF NON LATCH NON LATCH 20S TIME DELAY 10S TIME DELAY 20S...
  • Page 47: Relay Options & Programming

    “MAP ISO/FAULT” Up to 5 Zones in Isolate/Fault Relay Output Mapping A total of 64 expansion relays can be fitted to the IFS-2600. Each relay can be individually programmed to mimic any of the following; Standard Outputs which may be mimicked:...
  • Page 48 MAP -OR-, MAPPING = 1 TO 1 IE: RELAY 1 = ZONE 1, RELAY 2 = ZONE 2..... The IFS-2600 PANEL is self-configuring on power-up therefore it is not necessary to program the number of relay boards. Zone expansion boards fitted must have the correct jumper selected.
  • Page 49: Relay Programming

    IFS-2600 Fire Indicator Panel Section 5 Programming 5.3.2. Relay Programming Select RELAY # SELECT RELAY# (ALL) Use the "NEXT" & "PREVIOUS" keys to scroll through "ALL" "1" "2" "3” Up to 64 and then wrap around. Once the desired relay number has been selected, pressing the "SELECT" button will select it. Pressing "EXIT"...
  • Page 50 IFS-2600 Fire Indicator Panel Section 5 Programming RELAY Mapping RELAY #1 MAP (00) ** Relay mapping can only be selected if the relay is set as a MAP type. These 5 entry fields represent the zone numbers that the relay is to be mapped to and will be activated from.
  • Page 51: Global Options & Programming

    IFS-2600 Fire Indicator Panel Section 5 Programming 5.4. Global Options & Programming There are four global options that can be programmed: (ACF) RELAY TIME Use the "NEXT","PREVIOUS" & "SELECT" keys to select. Pressing "EXIT" will return to "Main Menu". Ancillary Control Facility (ACF)
  • Page 52: Alarm Verification

    IFS-2600 Fire Indicator Panel Section 5 Programming Alarm Verification Facility (AVF) Alarm verification (AVF) is a facility used to minimise false alarms. AVF only applies to the zones programmed for the AVF function. Global Programmable Options: Alarm Verification DISABLED 2 MINUTES...
  • Page 53: Print Programming Data

    IFS-2600 Fire Indicator Panel Section 5 Programming Use the "NEXT" & "PREVIOUS" keys to change the first relay to start from, together with the matching zone. Use the “ENTER” key to toggle between the two and press “SELECT” once finalised. “Exit” will abort unity map.
  • Page 54: Section 6 Appendix

    IFS-2600 Fire Indicator Panel Section 6 Appendix Section 6 Appendix 6.1. Appendix A Glossary of Terms Australian standard for; - AS-4428.1 Automatic Fire Detection and Alarm Systems Control and Indicating Equipment. Australian standard for; - AS-4428.5 Automatic Fire Detection and Alarm Systems Power Supply Units.
  • Page 55: Appendix B

    IFS-2600 Fire Indicator Panel Section 6 Appendix 6.2. Appendix B Summary of Terminations & Cautions MCP LOOP Used for the looping of the manual call point to a particular zone chosen for indication. This is achieved by wiring from the zone, to the MCP, to the MCP loop then out to the field with the EOL across the last detector.
  • Page 56 IFS-2600 Fire Indicator Panel Section 6 Appendix MIMIC DATA & CLOCK These outputs together with the mimic power terminals are used to serially communicate with the mimic panels when fitted. EOL resistor is not required on these lines. (Refer to Section 4.5 for more details.) NOTE: Firmware must be Version 6 or above for mimic operation.
  • Page 57: Appendix C

    IFS-2600 Fire Indicator Panel Section 6 Appendix 6.3. Appendix C IFS-2600 Programmed Options Global System Parameters Date: Latch ND Non-Latch ND Latch NE Non-Latch NE ACF Output Disabled 2 min 3 min 4 min 5 min Alarm Verification (AVF) Notes: Programmed by Place an "X"...
  • Page 58 IFS-2600 Fire Indicator Panel Section 6 Appendix ZONE TYPE PROGRAMMING Date: AZF No. Place an "X" in the appropriate box = Default DOC-01-009...
  • Page 59 IFS-2600 Fire Indicator Panel Section 6 Appendix AZF No. Place an "X" in the appropriate box = Default DOC-01-009...
  • Page 60 IFS-2600 Fire Indicator Panel Section 6 Appendix ZONE OUTPUT PROGRAMMING Date: INDICATE I-BELL IB- GENERAL IBG- ACF IBGA- BR1 IBGA- BR2 IBGA- BR1&BR2 Place an "X" in the appropriate box = Default DOC-01-009...
  • Page 61 IFS-2600 Fire Indicator Panel Section 6 Appendix AZF No. INDICATE I-BELL IB- GENERAL IBG-ACF IBGA- BR1 IBGA- BR2 IBGA- BR1&BR2 Place an "X" in the appropriate box = Default DOC-01-009...
  • Page 62 IFS-2600 Fire Indicator Panel Section 6 Appendix RELAY OUTPUT MAPPING Date: MAPPING MAINS BELL ISO/ FAIL Place an "X" in the appropriate box = Default DOC-01-009...
  • Page 63 IFS-2600 Fire Indicator Panel Section 6 Appendix MAPPING MAINS BELL ISO/ FAIL DOC-01-009...
  • Page 64: Technical Drawings

    IFS-2600 Fire Indicator Panel Technical Drawings 6.4. Technical Drawings 6.4.1. System Sensor Conventional Detector Connection Diagram DETA DETB DETB DET A DET B DET B TOPANEL TO PANEL BASE B401 BASE B401 CONVENTIONALDETECTORCONNECTIONDIAGRAM BASE B401 BASE B401 CONVENTIONAL DETECTOR CONNECTION DIAGRAM...
  • Page 65: Hochiki Conventional Detector Connection Diagram

    IFS-2600 Fire Indicator Panel Technical Drawings 6.4.2. Hochiki Conventional Detector Connection Diagram DET A DET B DET C TO PANEL CONNECTION FOR STANDARD DETECTORS AND BASES DET A DET B DET C BLUE TO PANEL WHITE CONNECTION FOR DFG-60BLKJ SEALED DETECTOR...
  • Page 66: Ancillary Connection Diagram

    IFS-2600 Fire Indicator Panel Technical Drawings 6.4.3. Ancillary Connection Diagram IFS - 2600 TYPICAL ANCILLARY CONNECTION DOC-01-009...
  • Page 67: Ase Connection Diagram

    IFS-2600 Fire Indicator Panel Technical Drawings 6.4.4. ASE Connection Diagram AC FAIL FAULT IFS2600 TERMINATION BRACKET PCB2004 ISOLATE CODE RED #10115 ROMTEK 10117 TYCO #10116 POWER 7 Columbia Court, Title Copyright Sheet: 2600 Norwest Business Park This document is & shall...
  • Page 68: Mimic Connection Diagram

    IFS-2600 Fire Indicator Panel Technical Drawings 6.4.5. MIMIC Connection Diagram PCB812 PCB812 PCB812 ZONES 1-8 ZONES 9-16 ZONES 17-24 IFS2600 PCB810 TERMINATION BOARD FITTED WITH IFS2600 MIMIC DRIVER 33-40 41-48 9-16 49-56 17-24 57-64 25-32 TP 0V Max 120 Meters MAF ISO 4/0.75mm cable...
  • Page 69: Dual Fan Connection Diagram

    IFS-2600 Fire Indicator Panel Technical Drawings 6.4.6. Dual Fan Connection Diagram FIRE PANEL FIELD WIRING FAN TERMINATION BOARD AUX POWER AUX +24 COMMON +VE START STOP AUX 0V START CONTROL START1 STOP FAN 1 FAN 1 START RELAY STOP1 FAN RUNNING...
  • Page 70: Exhaust Fan Connection Diagram

    IFS-2600 Fire Indicator Panel Technical Drawings 6.4.7. Exhaust Fan Connection Diagram FIRE PANEL FIELD WIRING FAN TERMINATION BOARD AUX POWER AUX +24 COMMON +VE START STOP AUX 0V START CONTROL START1 STOP FAN STOP RELAY STOP1 FAN RUNNING (MAPPED TO ACF FOR...
  • Page 71: Supply Fan Connection Diagram

    IFS-2600 Fire Indicator Panel Technical Drawings 6.4.8. Supply Fan Connection Diagram FIRE PANEL FIELD WIRING FAN TERMINATION BOARD AUX POWER AUX +24 COMMON +VE START STOP AUX 0V START CONTROL START1 STOP FAN START RELAY STOP1 FAN RUNNING (MAPPED TO ACF FOR...
  • Page 72: Smoke Spill Fan Connection Diagram

    IFS-2600 Fire Indicator Panel Technical Drawings 6.4.9. Smoke Spill Fan Connection Diagram FIRE PANEL FIELD WIRING FAN TERMINATION BOARD AUX POWER AUX +24 COMMON +VE START STOP AUX 0V START CONTROL START1 STOP FAN START RELAY STOP1 FAN RUNNING (MAPPED TO ACF FOR...
  • Page 73: Evac Connection Diagram

    IFS-2600 Fire Indicator Panel Technical Drawings 6.4.10. 10W EVAC Connection Diagram 10W EVAC FRONT PCB 908 PANEL EVAC CONTROL IFS2600 TERMINATION BOARD 4K7 5% SPEAKERS WITH 47K 5% LINK JP1 100V LINE TRANSFORMERS AND ISOLATION CAPACITORS WHITE BLACK/SHIELD MICROPHONE BLUE...
  • Page 74 NOTES...
  • Page 75 NOTES...
  • Page 76 New South Wales Queensland Victoria (Head Office) 24 Potts Street 32 Lambert Street 9 Columbia Way East Brisbane, QLD 4169 Richmond, VIC 3121 Baulkham Hills NSW 2153 ph +61 (0)7 3391 5777 ph +61 (0)3 9421 5552 ph +61 (02 9899-4155 fax +61 (0)2 9899-4156 fax +61 (0)7 3391 5800 fax +61 (0)3 9421 5553...