Timers - Mircom TX3 Series Installation Manual

Ul listed card access systems
Table of Contents

Advertisement

2.4

Timers

The following types of timers are associated with the Card Access System
operation:
2.4.1
Timer schedule
Events are scheduled as Always, Never, or administrator defined. Timed access
adheres to a schedule as follows:
Auto-unlock schedule. When enabled the door remains unlocked during the
schedule.
PIN required schedule. Card access requires the use of a PIN during the
schedule.
2.4.2
Unlock time
The door unlock timer starts when the door unlocks. When the timer expires the
door locks. The main door unlock timer is programmable from 0 to 300 seconds.
The default is 10 seconds.
2.4.3
Extended unlock time
This extended unlock timer mode is used for cards with the extended unlock
feature enabled. The timer starts when the door unlocks. When the extended
unlock timer expires the door locks. The timer resets when the main door sense is
programmed to be inactive. The extended unlock timer is programmable from 10
to 300 seconds. The default is 15 seconds.
2.4.4
Anti-passback
The anti-passback timer starts when access is granted. In this mode the user
cannot re-enter this door until the anti-passback timer expires. When the timer
expires the user has access. The anti-passback timer is programmable from 0 to
900 seconds. The default is 300 seconds.
UL Listed TX3-CX Card Access System Installation Manual
Version 2
LT-6906
Copyright 2019
Unlock time
Extended unlock time
Anti-passback
Door held open warning
Door held open alarm
Configurable Features
23

Hide quick links: