Setup Procedure

After the thermostat is installed, it is necessary to set it up for a particular
heating/cooling system. There are nine types of heating and cooling systems. Each
system type is setup using nine screens. The available choices displayed on the setup
screens depend on the type of system selected. Follow these directions to access the
setup screens.
1. Press and hold the MODE and VIEW buttons simultaneously for five
seconds to access the setup menus.
2. Press VIEW to select the parameter. A box appears around the selected
parameter.
3. Press the Arrow keys (▲▼) to choose the value of the selected parameter.
4. Use the MODE button to advance to the next setup screen.
Advance to
next Setup
Screen
MODE
Step to next
VIEW
selection on
current Setup
Screen

Setup Notes

The following are general setup notes.
NOTE: Refer to "System Connections" on page 8 for remote sensor connections to
the thermostat.
NOTE: The Offset option permits recalibration of the room temperature sensor.
There are various reasons why users may want to adjust the temperature. The
selection number is the number of degrees added or subtracted to the actual
temperature. The range is -6° to +6°F. Factory default is 0°. This adjustment changes
the actual regulated temperature, not just the display.
NOTE: The sensors are used for temperature and humidity averaging. Choose USE
to include each sensor, or OMIT to exclude each sensor in the averaging equation.
Sensors that have the same designation (for example, outdoor) are averaged together.
NOTE: The thermostat will not leave the setup mode unless a valid sensor selection
is made.
NOTE: When the Reverse SMODE Dir (reverse system mode direction) selection
is set to Yes on the Screen Options page, the arrow keys (▲ ▼) can be used to select