Setup; Network Wiring - Crestron CHV-THSTAT Operation And Installation Manual

Heating/cooling and humidity thermostat
Hide thumbs Also See for CHV-THSTAT:
Table of Contents

Advertisement

Crestron CHV-TSTAT and CHV-THSTAT

Setup

Operations and Installation Guide – DOC. 8163C

Network Wiring

NOTE: When installing network wiring, refer to the latest revision of the wiring
diagram(s) appropriate for your specific system configuration, available from the
Downloads | Product Manuals | Wiring Diagrams section of the Crestron website
(www.crestron.com).
When calculating the wire gauge for a particular Cresnet run, the length of the run
and the power factor of each network unit to be connected must be taken into
consideration. If Cresnet units are to be daisy-chained on the run, the power factor of
each unit to be daisy-chained must be added together to determine the power factor
of the entire chain. If the unit is a home-run from a Crestron system power supply
network port, the power factor of that unit is the power factor of the entire run. The
length of the run in feet and the power factor of the run should be used in the
following resistance equation to calculate the value on the right side of the equation.
Resistance Equation
40,000
Where:
R < L x PF
The required wire gauge should be chosen such that the resistance value is less than
the value calculated in the resistance equation. Refer to the table below.
Wire Gauge Values
RESISTANCE
WIRE GAUGE
4
6
10
15
13
Doubled CAT5
8.7
NOTE: All Cresnet wiring must consist of two twisted-pairs. One twisted pair is the
+24V conductor and the GND conductor and the other twisted pair is the Y
conductor and the Z conductor.
NOTE: For larger networks (i.e., greater than 28 network devices), it may be
necessary to add a Cresnet Hub/Repeater to maintain signal quality throughout the
network. Also, for networks with lengthy cable runs or varying types of network
equipment, it may be desirable to add a hub/repeater after only 20 network devices.
R = Resistance (refer to table below).
L = Length of run (or chain) in feet.
PF = Power factor of entire run (or chain).
16
18
20
22
Tripled CAT5
Thermostats: CHV-TSTAT and CHV-THSTAT • 7
Thermostats