Crestron CHV-THSTAT Operation And Installation Manual page 44

Heating/cooling and humidity thermostat
Hide thumbs Also See for CHV-THSTAT:
Table of Contents

Advertisement

Thermostats
DEVICE OPTIONS
SETUP: DEVICE OPTS
Network ID:
LCD Contrast
CHV-THSTAT
[v2.0, #D8000000]
Select Network ID: Valid entries are 03 to FE in
Hex to match the network ID set for the
thermostat in SIMPL Windows.
LCD Screen Contrast:
1 Lighter through 10 Darker
Displays Model number, Firmware version and
TSID.
DISPLAY OPTIONS
SETUP: DISP OPTIONS
Temperature Units:
Temp Display Offset:
Main Scn Lwr Obj:
Use 0.5 Deg C Step:
°F or °C – Display in Fahrenheit or Celsius.
Offset (-6 to +6°F) Allows the user to adjust the
displayed/regulated temperature.
Main Screen Lower Object
SB – Slab
OD – Outdoor
HM – Humidity NA – None
°C may be displayed in 0.5 units.
38 • Thermostats: CHV-TSTAT and CHV-THSTAT
Crestron CHV-TSTAT and CHV-THSTAT
Slab 2 – Single Stage Space Heat with Slab Maximum (Continued)
2A
5
Global Page – Temperature & humidity selection for
entire house if part of a Cresnet system.
Outdoor Page – Temperature & humidity of the
outside sensor.
Remote Function Page 1, 2 – Allows remote control
of other functions (for example: lights, alarms, etc.).
Reverse SMODE Dir – Allows arrow keys to select
mode functions in both directions.
F
0
0
SB
Y
SCREEN OPTIONS
SETUP: SCRN OPTIONS
Disp Global Page:
Disp Outdoor Page:
Disp Rem Func Pg1:
Disp Rem Func Pg2:
Reverse SMODE Dir
Continued on the following page.
Operations and Installation Guide – DOC. 8163C
Y
Y
Y
Y
N

Advertisement

Table of Contents
loading

This manual is also suitable for:

Chv-tstat

Table of Contents