Summary of Contents for Crestron CHV-TSTAT-FCU-PIR-10

  • Page 1 CHV-TSTAT-FCU-PIR-10 Supplemental Guide Crestron Electronics, Inc.
  • Page 2 Certain Crestron products contain open source software. For specific information, visit www.crestron.com/opensource. Crestron and the Crestron logo are either trademarks or registered trademarks of Crestron Electronics, Inc. in the United States and/or other countries. Other trademarks, registered trademarks, and trade names may be used in this document to refer to either the entities claiming the marks and names or their products.
  • Page 3 Contents Introduction Set Up the Thermostat Enter Setup Mode Navigate Setup Mode Configure the Thermostat Supplemental Guide — 7964B Contents • i...
  • Page 4 ii • Contents Supplemental Guide — 7964B...
  • Page 5 Introduction After installation, the Crestron® CHV-TSTAT-FCU-PIR-10 needs to be set up. Refer to the information that follows for an overview of the setup procedure. For more installation information on the CHV-TSTAT-FCU-PIR-10, refer to the CHV-TSTAT-FCU-PIR-10 Quick Start Guide (Doc. 7915) at crestron.com/manuals.
  • Page 6 Up (p) and Down (q) buttons to change the value for the selected item. Configure the Thermostat SETUP: SYSTEM Screen Use the Heat Type option to select the type of HVAC system that the thermostat is controlling. 2 • CHV-TSTAT-FCU-PIR-10 Supplemental Guide — 7964B...
  • Page 7 BOOKED TIMEOUT should be used in a room that is occupied regularly, such as in a booked hotel room. BOOKED TIMEOUT should be set for a longer period of time than UNBOOKED TIMEOUT to ensure that the room does not enter the vacancy state while regularly occupied. Supplemental Guide — 7964B CHV-TSTAT-FCU-PIR-10 • 3...
  • Page 8 The Heat, Cool, and Fan calls are settable via 0.1 V increments. When the device operates as a relay, Heat Call is relegated to ON or OFF. The PIR displays DETECTED when motion is detected. 4 • CHV-TSTAT-FCU-PIR-10 Supplemental Guide — 7964B...
  • Page 9 Set the Display Temp to N to only display the setpoint temperature on the front panel of the device. SETUP: FAN VOLTAGE Screen Use the SETUP: FAN VOLTAGE screen to select the voltages corresponding to the high, medium, and low fan speeds. Supplemental Guide — 7964B CHV-TSTAT-FCU-PIR-10 • 5...