Crestron CHV-THSTAT Operation And Installation Manual page 84

Heating/cooling and humidity thermostat
Hide thumbs Also See for CHV-THSTAT:
Table of Contents

Advertisement

Thermostats
Slot 6 – System Configuration (continued)
SIGNAL
ColdWeatherComp
DispGlobalPage
DispOutdoorPage
DispRemoteBtnPage1
DispRemoteBtnPage2
DispHumidityModePage
DispHumidityViewPage
Temp(DegF)
Temp(DegC)
0.5_Steps
MainScrnOb_NA
MainScrnOb_Outdoor
MainScrnOb_Humidity
MainScrnOb_SlabTemp
RevSmodeDir
78 • Thermostats: CHV-TSTAT and CHV-THSTAT
I/O
SIGNAL
DEFINITION
TYPE
Output
Digital
Indicates that cold weather compensation has been enabled.
Remains high for as long as the mode is enabled.
Outdoor low-temperature compensation modifies the humidifier
output to prevent condensation on windows in cold weather.
High/1 = Cold weather compensation enabled; Low/0 = Not
enabled
Indicates that the Global page (consisting of the Global Send
Output
Digital
button) has been enabled for display on the thermostat LCD.
Remains high for as long as the page is enabled.
High/1 = Global page enabled; Low/0 = Not enabled
Output
Digital
Indicates that the Outdoor page has been enabled for display on
the thermostat LCD. Remains high for as long as the page is
enabled.
The Outdoor Page displays the temperature and relative
humidity readings of outdoor sensors.
High/1 = Outdoor page enabled; Low/0 = Not enabled
Output
Digital
Indicates that Remote page 1 or 2 has been enabled for display.
Remains high for as long as the page is enabled.
The thermostats provide two Remote pages that can be used to
trigger non-HVAC functions such as AV control, lighting, or alarm
activation.
High/1 = Remote page enabled; Low/0 = Not enabled
Output
Digital
Indicates that the Humidity Mode page has been enabled for
display on the thermostat LCD. Remains high for as long as the
page is enabled.
The Humidity Mode page allows the user to enable or disable the
humidifier.
High/1 = Humidity Mode page enabled; Low/0 = Not enabled
Output
Digital
Indicates that the Humidity View page has been enabled for
display on the thermostat LCD. Remains high for as long as the
page is enabled.
The Humidity View Page displays the relative humidity and
setpoint values.
High/1 = Humidity View page enabled; Low/0 = Not enabled
Output
Digital
Indicates the temperature scale: Fahrenheit or Celsius.
Output
Digital
Indicates that the temperature in Celsius will be displayed in half
degrees if Celsius was selected.
Output
Digital
Reports the reading that will be displayed under the current
temperature on the Main page of the thermostat LCD.
The "Main screen object" can be outdoor temperature, slab
temperature, indoor humidity, or none (NA).
Output
Digital
Reverses the direction that the selection box moves for mode
screens.
High/1 = Up arrow moves box to left; Low/0 = Moves box to right
Continued on the following page
Crestron CHV-TSTAT and CHV-THSTAT
Operations and Installation Guide – DOC. 8163C

Advertisement

Table of Contents
loading

This manual is also suitable for:

Chv-tstat

Table of Contents