Thermostat Setup - Crestron CHV-TSTAT Operation And Installation Manual

Hide thumbs Also See for CHV-TSTAT:
Table of Contents

Advertisement

Thermostats
SETUP: SYSTEM
MODE
Heat Sys Type:
# Heat Stags:
# Cool Stags:
VIEW
Radiant /
Forced Air:
CRESTRON
SETUP: SYSTEM PERF
MODE
Heat Anticipator:
Cool Anticipator:
Auto Mode DdBand:
VIEW
HP Balance Pt:
AUX Balance Pt:
CRESTRON
14 • Thermostats: CHV-TSTAT and CHV-THSTAT

Thermostat Setup

After the thermostat is installed, it is necessary to set it up. Follow these directions.
Press and hold the MODE and VIEW buttons simultaneously for five seconds to
access the setup menus. The following setup screens appear in order: System Setup,
System Preferences, Humidity and Fan Options, Device Options, Screen Options,
Display Options, Sensors, and Service/Test. Use the MODE button to advance to the
next setup screen.
HEATING SYSTEM TYPE
Press VIEW to select the parameter: Heating System Type (Heat/Cool or heat pump),
Heat stages (1 or 2), Cool Stages (1 or 2), and radiant or forced air system. A box
appears around the selected parameter.
Press the Arrow keys (▲▼) to enter the value of the selected parameter.
Heat/Cool (H/C) or Heat Pump (Hpump)
H/C
1
One or Two Stages
1
F.Air
Forced Air or Radiant choice for Heat/Cool systems
HP/Aux or D.Fuel (Dual Fuel) choice for Heat Pump
SYSTEM PERFORMANCE
Press the MODE button to access the next menu, SETUP: SYSTEM
PERFORMANCE. Press VIEW to select preferences. Press the Arrow keys (▲▼) to
select the value of the parameter.
3
3
2
0
0
0
0
15
Crestron CHV-TSTAT and CHV-THSTAT
Anticipators
(valid selections are 1 through 6)
Low number = more frequent cycles and faster
response (tighter regulation)
High number = less frequent cycles and slower
response (looser regulation)
Auto Mode Dead Band
(valid selections are 2 through 6
The minimum differential between heating
and cooling setpoints
HP Balance Point (Heat Pump Systems only)
Minimum outdoor temperature at which the heat
pump will run (requires outdoor sensor)
AUX Balance Point (Heat Pump with Aux only)
Maximum outdoor temperature at which Aux Heat
System supplements the heat pump (requires
outdoor sensor)
Operations and Installation Guide – DOC. 8163
0
)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Chv-thstat

Table of Contents