Identity Code ....................... 8 Supplied Hardware ...................... 8 Installation ........................8 DIP Switch Setup ...................... 10 Wiring the CHV-TSTATEX-FCU to the HVAC System.......... 11 Basic Setup ..........................14 Basic Thermostat Setup..................... 14 Joining an infiNET EX Network ................14 Leaving an infiNET EX Network................15 Verifying Communication Status ................
Crestron automation system. Integrating HVAC with a Crestron system can help lower energy bills and increase user friendliness. The CHV-TSTATEX-FCU is designed for fan coil unit HVAC systems. The large backlit LCD display provides a clear view of temperature, set point, system mode, fan mode, system status, and setup functions.
Page 6
These settings allow HVAC contractors to install and test the thermostats prior to the appearance of a Crestron system integrator. An infiNET EX gateway such as the CEN-RFGW-EX or MC3 is needed for communications.
Crestron CHV-TSTATEX-FCU infiNET EX™ Thermostat (Fan Coil Unit) Specifications Specifications for the CHV-TSTATEX-FCU are listed in the following table. CHV-TSTATEX-FCU Specifications SPECIFICATION DETAILS Wireless RF Transceiver 2-way RF, 2.4 GHz ISM Channels 11-26 (2400 to 2483.6 MHz), IEEE 802.15.4 compliant Range (typical) 150 ft (46 m) indoor, 250 ft (76 m) outdoor;...
Page 8
Remote Temperature Sensor 3-Series Control System 1. The latest software versions can be obtained from the Crestron Web site. Refer to the NOTE following these footnotes. 2. Crestron 2-Series control systems include the AV2 and PRO2. Consult the latest Crestron Product Catalog for a complete list of 2-Series control systems.
CHV-TSTATEX-FCU. CHV-TSTATEX-FCU Physical View CHV-TSTATEX-FCU Overall Dimensions (Front and Side Views) 5.53 in 1.03 in (141 mm) (26 mm) 4.50 in (115 mm) infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 5 Operations & Installation Guide – DOC. 7206A...
Page 10
Cycles through available system modes: OFF, HEAT, AUTO and COOL. FAN Button Toggles fan setting between FAN AUTO and FAN ON. Raises the setpoint. (Continued on following page) 6 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
Page 11
Remote sensor return Remote sensor return Unused Heat Unused HVAC (4) Two-position terminal blocks. Fan low Fan medium Fan high Unused Cool 24V return 24V supply infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 7 Operations & Installation Guide – DOC. 7206A...
CEN-RFGW-EX wireless gateway requires a unique RF ID. The RF ID is a two-digit hexadecimal number that can range from 03 to FF. The RF ID of the unit, set using Crestron Toolbox™, must match the RF ID specified in the SIMPL Windows program.
Page 13
NOTE: To ensure accurate temperature readings, avoid drafts in the back of the unit by plugging the wire hole with insulation. 5. Attach the CHV-TSTATEX-FCU back plate to the electrical box using the two supplied #06-32 x 1” pan head screws.
NOTE: In Steal Power mode, even when an auxiliary power source is available, the unit will continue to enter a communications sleep state, waking every 30 seconds or 10 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
The illustrations on the following pages show examples for connection to various types of HVAC systems. If your system does not match any of the systems described below, contact Crestron Technical Support for assistance. Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 11...
Page 16
NOTE: 24 Volt power is returned through the R connector. Refer to wiring diagrams on the following pages. NOTE: Refer to “DIP Switch Setup” which starts on page 10 for DIP switch settings. 12 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
Page 17
CHV-TSTATEX-FCU Wiring Diagram Heat Pipe Valve Cool Pipe Valve Fan High Relay Fan Med Relay Fan Low Relay System Transformer Optional CHV-TSTATEX-FCU Sensor Wiring CHV-RTS Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 13...
# represents an error code. 6. Once all devices have been acquired, take the CEN-RFGW-EX out of Acquire mode. Press FAN on the thermostat to exit Setup mode. 14 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
Network link to gateway is not desirable. cost debugging to improve Communication may work ok but is subject to communications. many hops that will impact communication speed and battery life. Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 15...
“—” when a function is selected. All other display elements will be hidden (refer to “LCD Display” which starts on page 23). 16 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
(tighter regulation). Higher setting results in less frequent cycles and slower response (looser regulation). The default value should suffice in nearly all installations. (Continued on following page) Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 17...
Page 22
Button not held long button for three seconds enough (Er) for this function to execute. (Continued on following page) 18 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
Page 23
Crestron customer service team by (flashing --) calling Crestron at Finished, self test ok 1-888-CRESTRON (00) (1-888-273-7876). Finished, self test failed (E#, where # represents an error code) Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 19...
The flashing icon will time out after five seconds of no button activity. b. In single setpoint Auto mode, use the buttons to adjust the setpoint as usual. 20 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
The setpoint is the user selectable temperature you want the system to maintain. buttons will change the current setpoint by one degree F or C. Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 21...
If the thermostat is wired to have the optional 24 VAC at the 24C terminal and the power switch is set for 24V, there will not be a delay in feedback. LCD Display CHV-TSTATEX-FCU LCD Display AUTO Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 23...
Page 28
* When the CHV-TSTATEX-FCU detects a low battery condition (approximately one month of battery life remaining), the display will alternate “Lo” in place of the ambient temperature once per second. 24 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
The available toolboxes differ depending on the View but all Views include a "General" toolbox that allows you to add areas and rooms at any time. Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 25...
Remotes (RF) folder of the Device Library and drop it on the CEN-RFGW-EX. Locating the CHV-TSTATEX-FCU in the Device Library NOTE: If connecting to the MC3, drag the CHV-TSTATEX-FCU directly to the control system. 26 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
Page 31
The symbol can be viewed by double clicking on the icon or dragging it into Detail View. Each signal in the symbol is described in the SIMPL Windows help file (F1). Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 27...
2-Series Control Systems Reference Guide (Doc. 6256). If connecting to the MC3, refer to the latest version of the MC3 3-Series Control System Operations Guide (Doc. 7095). 28 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
CHV-TSTATEX-FCU (CEN-RFGW-EX). Right-click on the CHV-TSTATEX-FCU (CEN-RFGW-EX) to display actions that can be performed on the CHV-TSTATEX-FCU (CEN-RFGW-EX). Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 29...
Anticipator setting Reprogram anticipator setting (refer to too quickly. is too low. “Setup Mode Parameters/Functions” which starts on page 17). (Continued on following page) 30 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
Page 35
17). Bad location. Ensure the thermostat is located away from direct sunlight, drafts, doorways, skylights and windows or exterior walls. (Continued on following page) Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 31...
Documentation revision. Check the Crestron Web site periodically for manual update availability and its relevance. Updates are identified as an “Addendum” in the Download column. 32 • infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206A...
The user selectable temperature you want the system to maintain. Time Delay (Timer Guards) Refers to a safety device or circuit that will not allow restart for three minutes. Operations & Installation Guide – DOC. 7206A infiNET EX™ Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU • 33...
Purchasers should inquire of the dealer regarding the nature and extent of the dealer's warranty, if any. CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for which it was intended or if it has been subjected to misuse, accidental damage, modification or improper installation procedures.