SMC Networks PF3A801H-L Operation Manual page 86

Digital flow switch modular type
Hide thumbs Also See for PF3A801H-L:
Table of Contents

Advertisement

●Product individual parameters (continued)
Index
Access
Sub
1
index
dec
hex
1
R/W
1430 0x0596
2
R/W
1
R/W
2
R/W
3
R/W
1440 0x05A0
4
R/W
5
R/W
6
R/W
7
R/W
1
R/W
1450 0x05AA
2
R/W
1
R/W
2
R/W
3
R/W
1460 0x05B4
4
R/W
5
R/W
6
R/W
7
R/W
Data
Initial
Parameter
type
value
2
ModE2
(Selection of output
U8
0
mode)
2ot
U8
0
(Selection of output
type)
P_2 (n_2)
S16
250
(Selection of output
set value)
H_2
U16
25
(Setting of OUT1
hysteresis)
P2L (n2L)
(Lower limit of window
S16
150
comparator)
P2H (n2H)
S16
300
(Upper limit of window
comparator)
WH2
U16
50
(Window comparator
hysteresis)
dtH2
U16
0
(Delay time ON)
dtL2
U16
0
(Delay time OFF)
ModE2
(Selection of output
U8
0
mode)
2ot
(Selection of output
U8
0
type)
P_2 (n_2)
S16
500
(Selection of output
set value)
H_2
U16
50
(Setting of OUT1
hysteresis)
P2L (n2L)
(Lower limit of window
S16
300
comparator)
P2H (n2H)
S16
600
(Upper limit of window
comparator)
WH2
U16
100
(Window comparator
hysteresis)
dtH2
U16
0
(Delay time ON)
dtL2
U16
0
(Delay time OFF)
-85-
Data
4
storage
Set value
3
0: HYS (Hysteresis)
Y
1: Wind
(Window comparator)
0: 1_P (Normal output)
Y
1: 1_n (Reverse output)
Setting range
Y
0xFF9C to 0x0258
(-100 to 600)
Setting range
Y
0x0000 to 0x02BC
(0 to 700)
Setting range
Y
0xFF9C to 0x0258
(-100 to 600)
Setting range
Y
0xFF9C to 0x0258
(-100 to 600)
Setting range
Y
0x000 to 0x015E
(0 to 350)
Y
Setting range
0x0000 to 0x1770
(0 to 6000)
Y
0: HYS (Hysteresis)
Y
1: Wind
(Window comparator)
0: 1_P (Normal output)
Y
1: 1_n (Reverse output)
Setting range
Y
0xFFCE to 0x041A
(-50 to 1050)
Setting range
Y
0x0000 to 0x044C
(0 to 1100)
Setting range
Y
0xFFCE to 0x041A
(-50 to 1050)
Setting range
Y
0xFFCE to 0x041A
(-50 to 1050)
Setting range
Y
0x0000 to 0x0226
(0 to 550)
Y
Setting range
0x0000 to 0x1770
(0 to 6000)
Y
Remarks
Setting of OUT2 output normal and
reserved output
Setting of OUT2 output set value
(Hysteresis)
Setting of OUT2 hysteresis
(Hysteresis)
Setting of OUT2 output set value
(Lower limit of window comparator)
Setting of OUT2 output set value
(Upper limit of window comparator)
Setting of OUT2 hysteresis
(Window comparator)
Setting of OUT2 delay time ON
10 ms increments
Setting of OUT2 delay time OFF
10 ms increments
Setting of OUT2 output normal and
reserved output
Setting of OUT2 output set value
(Hysteresis)
Setting of OUT2 hysteresis
(Hysteresis)
Setting of OUT2 output set value
(Lower limit of window comparator)
Setting of OUT2 output set value
(Upper limit of window comparator)
Setting of OUT2 hysteresis
(Window comparator)
Setting of OUT2 delay time ON
10 ms increments
Setting of OUT2 delay time OFF
10 ms increments
No.PF※※-OMY0005