Advertisement

Change of Set Value [3 step setting mode]

3 step setting mode
In the 3 step setting mode, the set value selected in the display and the hysteresis can be changed in just 3
steps.
Use this mode if the product is to be used straight away, after changing only the set values.
(The current measured value is displayed on the main display.)

■Default setting

When the flow exceeds the set value [P_1], the switch will be turned ON.
When the flow falls below the set value by the amount of hysteresis [H_1] or more, the switch will turn OFF.
If the operation shown below is acceptable, then keep these settings.
●PF3A801H
Item
[P_1] Set value of OUT1
[H_1] Hysteresis of OUT1
[P_2] Set value of OUT2
[H_2] Hysteresis of OUT2
●PF3A802H
Item
[P_1] Set value of OUT1
[H_1] Hysteresis of OUT1
[P_2] Set value of OUT2
[H_2] Hysteresis of OUT2
: For hysteresis, please refer to [F 1] Setting of OUT1 (page 37).
Default Settings
500 L/min
50 L/min
500 L/min
50 L/min
Default Settings
1000 L/min
100 L/min
1000 L/min
100 L/min
-26-
No.PF※※-OMY0005