F30 Setting Of Accumulated Value Hold - SMC Networks PF3A801H-L Operation Manual

Digital flow switch modular type
Hide thumbs Also See for PF3A801H-L:
Table of Contents

Advertisement

■[F30] Setting of accumulated value hold
In the default setting, the accumulated flow value is not held when the power supply is turned off.
This function enables the accumulated flow value to be stored in permanent memory every 2 or 5 minutes.
: When using the accumulated value hold function, calculate the product life from the operating conditions, and use the product within
its life. Maximum updating time of the accumulated value is 1.5 million times.
If the product is operated 24 hours per day, the product life will be as follows.
•Data memorized every 5 minutes: 5 minutes x 1.5 million times = 7.5 million minutes = 14.3 years
•Data memorized every 2 minutes: 2 minutes x 1.5 million times = 3 million minutes = 5.7 years
If the Accumulated Flow External Reset is repeatedly used, the product life will be shorter than calculated life.
<Operation>
Display [F30] by pressing UP or DOWN button in function selection mode.
Select accumulated value hold
Press the UP or DOWN button to select the accumulate value hold.
Press the SET button to set.
: The value is stored in memory every 2 or 5 minutes. If the power supply is turned off, the accumulated flow since the last time it was
stored will be lost.
: When the power supply is turned on again, the accumulated flow count will start from the last value recorded at B.
Press the SET button.
[F30] Setting of accumulated value hold completed
-53-
Move on to select accumulated value hold.
Return to function selection mode.
No.PF※※-OMY0005

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pf3a802h-l

Table of Contents