WAGO 750-563 Manual page 47

I/o modules fieldbus independent. 2 ao 0/4-20ma / 6-18v dc 16 bit. for wago-i/o-system 750
Table of Contents

Advertisement

2.1.1.11
Fieldbus-Specific Behavior
2.1.1.11.1
Default Mapping
2.1.1.11.2
Mapping for Couplers/Controllers with Word-Alignment
Valid for: 750-841, 750-842
WAGO-I/O-SYSTEM 750
I/O Modules
Byte
Input data
0
S0
Status byte 0
1
D0
Not used
2
D1
Not used
3
S1
Status byte 1
4
D2
Not used
5
D3
Not used
Byte
Input data
0
S0
Status byte 0
1
---
Fill byte for word alignment
2
D0
Not used
3
D1
Not used
4
S1
Status byte 1
5
---
Fill byte for word alignment
6
D2
Not used
7
D3
Not used
750-563 [2 AO 0/4-20mA / 6-18V DC 16 Bit]
Fieldbus-Specific Behavior
C0
D0
D1
C1
D2
D3
C0
---
D0
D1
C1
---
D2
D3
Output data
Control byte 0
Output data word 1 (LSB)
Output data word 1 (MSB)
Control byte 1
Output data word 2 (LSB)
Output data word 2 (MSB)
Output data
Control byte 0
Fill byte for word alignment
Output data word 1 (LSB)
Output data word 1 (MSB)
Control byte 1
Fill byte for word alignment
Output data word 2 (LSB)
Output data word 2 (MSB)