Write/Read Process - WAGO 750-563 Manual

I/o modules fieldbus independent. 2 ao 0/4-20ma / 6-18v dc 16 bit. for wago-i/o-system 750
Table of Contents

Advertisement

2.1.1.9.4.3 Write/Read Process

Request (application)
Parameter
TGL_MS
PRM_RW
MORE_PRM
A0 ... A7
PRM0 ...
PRM15
Response (I/O module)
Parameter
TGL_SM
A0 ... A7
TIMEOUT
BUF_OFL
PRM_ERR
PRM0 ...
PRM15
The module uses the error flags TIMEOUT, BUF_OV and PRM_ERR to
report errors during the parameter data exchange.
After the last parameter data has been sent to the module (MORE_PRM =
FALSE), the module checks the entire parameter set and accepts it if
everything is correct. Otherwise, the module returns a parameter error
(PRM_ERR = TRUE).
WAGO-I/O-SYSTEM 750
I/O Modules
750-563 [2 AO 0/4-20mA / 6-18V DC 16 Bit]
Value
Meaning
!= TGL_SM
Initiate instruction
0
Read access
1
Write access
0
Parameter data transmission is completed with the
currently-transmitted parameter.
1
More parameter data to follow.
0 ... (n-1)
Parameter address
0 ...65535
Parameter data write access
Value
Meaning
== TGL_MS
Instruction completed
0 ... (n-1)
Address parameter data mirrored
0
Monitoring time not expired
1
Monitoring time expired
0
Access within the module parameter range
1
Access outside the module parameter range
0
No parameter/parameter set error
1
Parameter/parameter set error
0 ...65535
Parameter data read access
Parameter Setting
• 33