Setting the numeric display (cf. register 32, bit 3, and bit 6)
Bit 6
Register
16 bit integer value with leading sign. The user scaling is activated or deactivated via bit 0 in
register 32.
Y
1
Register
16 bit fixed point value without leading sign. The user scaling is activated or deactivated via
bit 0 in register 32.
Y
1
Register
16 bit in X
The substitute value is placed on the output of the module after a system reset or an I/O
module timeout (module has received no process data for 100 ms).
The substitute value is selected via register 32, bit 9.
Register
16 bit integer value with leading sign. The user calibration is active if bit 1 is not set in
register 32.
Y
DAC
WAGO-I/O-SYSTEM 750
I/O Modules
Bit 3
Display
0
X
0 ... 65535
1
0
Twos complement
Leading
1
1
sign/amount
Funvtion
33
User scaling offset
= X
* R34 / 256 + R33
IN
Function
34
User scaling gain
= X
* R34 / 256 + R33
IN
Function
35
User substitute value
coordinates, depending on the numeric format.
IN
Function
36
User calibration offset
= Y
* R37 / 8192 + R36
3
750-563 [2 AO 0/4-20mA / 6-18V DC 16 Bit]
0 mA
4 mA
6 V
0x0000
0x7FFF
!
0
32767
0x8000
0xFFFF
!
-32768
0xFFFF
0x8001
!
-32767
Memory
Access
RAM
Memory
Access
RAM
Memory
Access
RAM
Memory
Access
RAM
Parameter Setting
0x8000
0xFFFF
!
32768
0x0001
0x7FFF
!
-1
0
0x0001
0x7FFF
!
-1
Factory setting
R/W
0x0000
Factory setting
R/W
0x0100
Factory setting
R/W
0x0000
Factory setting
R/W
0xXXXX
• 23
20 mA
20 mA
18 V
65535
32767
32767