Messages About The Mode - Siemens PROFINET SIRIUS 3RW5 Equipment Manual

Soft starters and solid-state switching devices
Hide thumbs Also See for PROFINET SIRIUS 3RW5:
Table of Contents

Advertisement

7.7

Messages about the mode

The following message bits in data set 92 of the 3RW5 soft starter (slot 2) (Page 168) clearly
indicate which control source currently has control priority:
• Automatic mode (
• Automatic operation - input controlled (
• Operating mode manual - bus (
• Manual operation bus - PC controlled (
• Manual operation bus - Webserver controlled (
• Operating mode manual - local (
• Manual operation local - input controlled (
• Manual operation local - HMI controlled (
• Manual operation local - PC controlled (
• Connection abort in manual mode (
Automatic
Manual
Manual operation
bus
1)
0
0
0
1
0
0
0
1
0
0
0
1
0
0
1
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
Supported by soft starter 3RW55 with firmware version V2.1 or higher and soft starter 3RW55 Failsafe with firmware version
1)
V1.1.0 or higher
Combination of the message bits not possible for 3RW50, 3RW52, 3RW55 soft starters with firmware version earlier than V2.1
2)
and 3RW55 Failsafe soft starters with firmware version V1.0.0. For soft starters 3RW55 from firmware version V2.1 and soft
starters 3RW55 Failsafe with firmware version V1.1.0 or higher if the digital inputs have master control by activating the
"Manual operation local - input controlled" bit in the process image output (PIQ). The PLC can fetch back control at any time.
3)
Combining the message bits is possible for 3RW50, 3RW52, 3RW55 and 3RW55 Failsafe soft starters. For soft starters 3RW55
from firmware version V2.1 and soft starters 3RW55 Failsafe with firmware version V1.1.0 or higher only if the input action
"Operating mode manual - local" has been parameterized and activated.
For more information on setting the operating mode, see chapter Operating modes and master
control function (Page 24).
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
)
Manual operation local
0
0
0
0
0
0
0
0
0
0
1
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
1
0
0
0
1
1
0
0
1
0
0
0
1
0
)
1)
)
)
)
)
)
)
)
)
Control priority is with:
0
0
0
Message is not permitted.
0
0
0
PLC controls via fieldbus.
0
0
0
Control digital inputs.
0
0
1
No control source.
0
0
0
PC controls via fieldbus.
0
0
0
Web server controls via fieldbus.
0
0
1
No control source.
0
0
0
Input IN or control digital inputs.
1
0
0
HMI controls.
0
1
0
PC controls via local interface.
Messages and diagnostics
7.7 Messages about the mode
2)
3)
81

Advertisement

Table of Contents
loading

Table of Contents