Commands
ID
Modifier
0x10
-
0x01
0x02
Result
After receiving the command, the 3RW5 soft starter sends the requested information or an error
message.
Measured values
The measured values are uniquely identified by IDs. Dependent on the 3RW5 soft starter, the
following measured values are supported:
ID
Measured value
7
Phase current IL1 (rms)
8
Phase current IL2 (rms)
9
Phase current IL3 (rms)
33
Phase current average (rms)
34
Active power
200
Active energy import (total)
Supported by SIRIUS 3RW50 soft starter
1)
Supported by SIRIUS 3RW52 soft starter from firmware version V2.0
2)
Supported by SIRIUS 3RW55 soft starter from firmware version V2.0
3)
4)
Supported by SIRIUS 3RW55 Failsafe soft starter
Accuracy of the specifications
The current values are transferred with the following tolerances:
• Accuracy Domain (unsigned8) = 0x03 → according to IEC 61557‑12
• Accuracy Class (unsigned8) = 0x11 → 5%
• Range (Float32) = I
It follows that the measured values are transferred with an accuracy of 5% relative to the
maximum configurable rated operational current I
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
Command
Query_Measurement
Get_Measurement_List
Get_Measurement_Values
(fixed value parameter)
e_max
Description
-
Command for providing a list of supported PROFIenergy measured
values.
Command for providing the supported PROFIenergy measured val‐
ues.
Unit
A
A
A
A
W
Wh
.
e
Functions
8.1 PROFIenergy
3RW
50
1)
52
2)
55
3)
55-F
4)
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
-
-
x
x
-
-
x
x
89