4. Set the device name configured in the configuration software of the controller on the
3RW5 soft starter.
The following procedures are possible:
– Via SIRIUS Soft Starter ES (TIA Portal) Premium / Professional on the 3RW5 communication
– Via SIRIUS Soft Starter ES (TIA Portal) over the local interface on the 3RW5 HMI High
– Via the 3RW5 HMI High Feature
Note the information in chapter Device name (Page 60).
5. Set the IP parameters in the 3RW5 communication module.
The following procedures are possible:
– During startup, the IO controller issues the IP parameters based on the device name and
– The IP parameters of the IO device are transferred online to the 3RW5 communication
– Via SIRIUS Soft Starter ES (TIA Portal) Premium / Professional on the 3RW5 communication
– Via SIRIUS Soft Starter ES (TIA Portal) over the local interface on the 3RW5 HMI High
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
module
Brief overview: Window "Project Navigation" with current project under created Soft
Starter > "Online & Diagnostics" > Window "Work area" > "PROFINET IO ST /
PROFINET IO HF > Functions > Assign PROFINET device name"
Brief overview: Window "Project Navigation" with current project under created Soft
Starter > "Device configuration" > Window "Work area" > Communication module
"PROFINET IO ST / PROFINET IO HF" > Inspector window "PROFINET IO ST /
PROFINET IO HF" > Tab "Properties" > Tab "General" > "PROFINET interface > Ethernet
addresses > PROFINET"
Feature
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
via 3RW5 communication module
Menu: "Parameter > Communication module > PROFINET / PROFINET HF > Device name"
You will find more information on operating the 3RW5 HMI High Feature in the Equipment
Manual of the 3RW5 soft starter.
assigns these to the IO device (temporary IP parameters).
module (static IP parameters).
module
Brief overview: Window "Project Navigation" with current project under created Soft
Starter > "Online & Diagnostics" > Window "Work area" > "PROFINET IO ST /
PROFINET IO HF > Functions > Assign IP address"
Brief overview: Window "Project Navigation" with current project under created Soft
Starter > "Device configuration" > Window "Work area" > Communication module
"PROFINET IO ST / PROFINET IO HF" > Inspector window "PROFINET IO ST /
PROFINET IO HF" > Tab "Properties" > Tab "General" > "PROFINET interface > Ethernet
addresses > IP protocol"
Feature
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
via 3RW5 communication module
6.2 Configuring the 3RW5 Soft Starter