Opc Ua Session Time-Out - Siemens PROFINET SIRIUS 3RW5 Equipment Manual

Soft starters and solid-state switching devices
Hide thumbs Also See for PROFINET SIRIUS 3RW5:
Table of Contents

Advertisement

Parameter
Parameter
No Security
Basic128RSA15 - sign
Basic128RSA15 - sign and encrypt
Basic256 - sign
Basic256 - sign and encrypt
Basic256SHA256 - sign
Basic256SHA256 - sign and encrypt
8.4.6

OPC UA Session Time-Out

The parameter "OPC UA Session Time-Out" determines how long an OPC UA client connection
remains open without activity. If the OPC UA client does not make a service request within this
time interval, the OPC UA server terminates the OPC UA client connection.
Setting options
• 3RW5 HMI High Feature (firmware version V3.1 or higher)
Menu: "Parameter > Communication Module > OPC UA server" (if the OPC UA server is
activated)
You will find more information on operating the 3RW5 HMI High Feature in the Equipment
Manual of the 3RW5 soft starter.
• User program via data set 132 (Page 163)
Parameter
Parameter
OPC UA Session Time-Out
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
Description
Disable (factory setting)
Enable
Disable (factory setting)
Enable
Disable (factory setting)
Enable
Disable (factory setting)
Enable
Disable (factory setting)
Enable
Disable (factory setting)
Enable
Disable
Enable (factory setting)
Description
SecurityPolicy
None
Basic128RSA15
Basic128RSA15
Basic256
Basic256
Basic256SHA256
Basic256SHA256
Factory setting: 30 s
Adjustment range: 10 ... 600 s
In steps of: 1 ms
Functions
8.4 OPC UA server
MessageSecurity‐
Mode
NONE
SIGN
SIGNANDENCRYPT
SIGN
SIGNANDENCRYPT
SIGN
SIGNANDENCRYPT
115

Advertisement

Table of Contents
loading

Table of Contents