Messages and diagnostics

7.6 Errors and remedial measures on the 3RW5 communication module

7.5.1

Disable or enable group error and group warning via 3RW5 HMI High Feature

Requirements
• Access protection to 3RW5 HMI High Feature is not active or has been removed.
• You are in the following menu:
– 3RW5 HMI High Feature with firmware version earlier than V2.0:
– 3RW5 HMI High Feature as of firmware version V2.0:
• You will find more information on operating the 3RW5 HMI High Feature in the Equipment
Manual of the 3RW5 soft starter.
Procedure
1. Select the desired menu item.
– "Group error"
– "Group warning"
2. Select a parameter.
– "Disable"
– "Enable" (factory setting)
3. Confirm the parameter.
Result
You have disabled or enabled transmission of error interrupts (group error) and maintenance
interrupts (group warning) via the bus connection.
7.6
Errors and remedial measures on the 3RW5 communication
module
The following table describes possible errors and remedies for the 3RW5 communication
module. Errors and remedies for the 3RW5 soft starter can be found in the Equipment Manual
of the 3RW5 soft starter.
Error No.
1)
303
1)
Visible on the display of the 3RW5 HMI Standard.
80
"Parameters > Communication module > PROFINET / PROFINET HF > Group diagnostics"
"Parameters > Communication module > Group diagnostics"
Error
Cause
Bus error
-
Remedy
Check the bus connection.
Check the bus parameters.
The error is acknowledged automatically
once it has been rectified.
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004