In "Automatic" mode, the PLC specifies the process image of the outputs. In this case, reading of
data set 68 returns the process image of the outputs as transmitted by the PLC.
Additional information
The following table describes the assignment of the process images "Parameter set bit 0" and
"Parameter set bit 1":
Parameter set
Process image error
Parameter set 1 (PS1)
Parameter set 2 (PS2)
Parameter set 3 (PS3)
A.4.5.2

Data set 69: Process image input (PII)

Only read (r) access to the process image inputs (PII) is possible.
Byte
Data format
0
Unsigned8
2
Unsigned8
4
Unsigned16
6
Unsigned16
Supported by SIRIUS 3RW50 soft starter
1)
2)
Supported by SIRIUS 3RW52 soft starter
Supported by SIRIUS soft starter 3RW55 and 3RW55 Failsafe
3)
Byte
Bit
Data format
12
0
Bool
1
Bool
2
Bool
3
Bool
4
Bool
5
Bool
6
Bool
7
Bool
166
Meaning
Coordination
Slot number
Length of data structure
Start position
Process image
Ready (automatic)
Motor On
Group error
Group warning
Input 1
Input 2
Input 3
Input 4
Parameter set bit 0
1
0
1
0
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
Parameter set bit 1
1
0
0
1
3RW
50
1)
52
2)
x
x
x
x
x
x
x
x
3RW
50
52
1)
2)
r
r
r
r
r
r
r
r
r
r
-
-
-
-
-
-
55 /
55-F
3)
x
x
x
x
55 /
55-F
3)
r
r
r
r
r
r
r
r