Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master
Control > Get Control"
Note
Fetching control from "Automatic operation - input controlled" mode
The "Automatic operation - input controlled" mode is possible for the following 3RW5 soft
starters:
• 3RW55 soft starter from firmware version V2.1
• Soft starter 3RW55 Failsafe with firmware version V1.1.0 or higher
Giving back control
SIRIUS Soft Starter ES (TIA Portal) Premium / Professional actively passes master control to
"Automatic" mode in response to a command to this effect.
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Control >
Release Control"
Withdrawal of control by other control sources
Control is withdrawn from the operating mode "Manual operation bus - PC controlled" by the
operating mode "Manual operation - local" as follows:
• 3RW50, 3RW52 soft starters and for 3RW55 and 3RW55 Failsafe soft starters if the input
action "Operating mode manual - local" is not parameterized: By activating the "Manual
operation local - input controlled" bit in the process image output (PIQ) (Page 154).
• For 3RW55 and 3RW55 Failsafe soft starters if the input action "Operating mode manual -
local" is parameterized: By activating the input action "Operating mode manual - local".
• "LOCAL / REMOTE" action on the 3RW5 HMI
• Command in SIRIUS Soft Starter ES (TIA Portal) (local interface on the 3RW5 HMI High
Feature)
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master
Control > Get Control"
Operating mode "Manual operation bus - Webserver controlled"
Fetching control
The web server actively fetches master control from the "Automatic" mode or "Automatic
operation - input controlled" mode in response to a command to this effect.
Web page "Control Panel" > "Master Control > Get Control"
Giving back control
The web server actively passes master control to "Automatic" mode in response to a command
to this effect.
Web page "Control Panel" > "Master Control > Release Control"
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
3.5 Operating modes and master control function
Description