Page 1
SIRIUS 3RW5 EtherNet/IP communication module Siemens Industry Online Support Safety information Industrial Controls Description Installing and removing Soft starters and solid-state switching devices Connection SIRIUS 3RW5 EtherNet/IP communication module Configuring Equipment Manual Messages and diagnosis Maintenance and service Technical data...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Table of contents Siemens Industry Online Support ......................7 Support Request ........................9 Additional documentation ....................... 10 Safety information ..........................13 Security information ........................ 13 ESD Guidelines ........................14 Data security in automation ....................16 Recycling and disposal ......................18 Description ............................
Page 4
Performing firmware update with micro SD card (3RW5 HMI High Feature) ......85 Replacing the 3RW5 communication module ................ 86 Restoring factory setting ......................88 Technical data ............................91 Technical data in Siemens Industry Online Support .............. 91 Dimension drawings ..........................93 10.1 CAx data ..........................93 10.2...
Siemens Industry Online Support Information and service At Siemens Industry Online Support you can obtain up-to-date information from our global support database: ● Product support ● Application examples ● Forum ● mySupport Link: Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/) Product support...
Page 8
Register your Siemens products, systems and software. Siemens Industry Online Support app The Siemens Industry Online Support app provides you access to all the device-specific information available on the Siemens Industry Online Support portal for a particular article number, such as operating instructions, manuals, data sheets, FAQs etc.
Siemens Industry Online Support 1.1 Support Request Support Request Use the Support Request online form to send your question directly to Technical Support: Support Request: Internet (https://support.industry.siemens.com/My/ww/en/requests) SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
(https://support.industry.siemens.com/cs/ww/en/view/1214574) ● Online help for SIRIUS Soft Starter ES (TIA Portal) ● Online help for STEP 7 ● The EMC Directive 2014/30/EU in practice (http://www.siemens.com/emc-guideline) ● Industrial Control Panels and Electronic Equipment of Industrial Machinery for North America (http://www.siemens.com/UL508A) ● Control Panels compliant with IEC Standards and European Directives (http://www.siemens.com/iec60204)
Page 11
Siemens Industry Online Support 1.2 Additional documentation Interesting links ● Manuals in Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/man) ● FAQs for 3RW5 Soft Starters (https://support.industry.siemens.com/cs/ww/en/ps/16212/faq) ● Downloads for 3RW5 Soft Starters (https://support.industry.siemens.com/cs/ww/en/ps/16212/dl) ● Catalog IC 10 (https://support.industry.siemens.com/cs/ww/en/view/109747945) ● Product support for STEP 7 (TIA Portal) (https://support.industry.siemens.com/cs/ww/en/ps/14672)
Page 12
Siemens Industry Online Support 1.2 Additional documentation SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
The damage caused to a device by overvoltage is usually not immediately evident and is only noticed after an extended period of operation. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 15
PCB traces. In this way, the discharged energy cannot reach or damage sensitive devices. Discharge your body before taking any necessary measurements on a device. Do so by touching grounded metallic parts. Use only grounded measuring instruments. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
● Trojan horses ● Unauthorized access ● Password phishing. Password phishing means attempting to get a user to divulge access data and passwords by masquerading as a different identity in an e-mail. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 17
VDI guideline "VDI/VDE 2182 Sheet 1, IT Security for Industrial Automation - General Model". You will find the guideline under "VDI Standards" on the VDI home page (https://www.vdi.de/richtlinien). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
For environmentally friendly recycling and disposal of your old device, please contact a company certified for the disposal of old electrical and/or electronic devices and dispose of the device in accordance with the regulations in your country. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Rockwell Studio 5000 with EDS file ● Parameterization software (optional), e.g. SIRIUS Soft Starter ES (TIA Portal) (Page 36) (only possible via local interface on the 3RW5 HMI High Feature) SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 20
Further information about ODVA and technologies protected by ODVA can be found on the ODVA website (https://www.odva.org). Target group The manual is intended for everyone involved in the following tasks: ● Planning and configuring systems ● Installation ● Commissioning ● Service and maintenance SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Description 3.1 History History Release number New features 05/2019 Initial release • 03/2020 Revision of the manual • Supplementing the contents for the 3RW50 and 3RW55 Failsafe Soft Starters • SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Firmware version of the 3RW5 communication module as delivered ⑥ MAC address ⑦ Article number ⑧ Fieldbus connection (RJ45 socket) ⑨ Product version ⑩ Plug-in connection to the 3RW5 Soft Starter with cover cap SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
● Minimum ENIP IO update time: 5 ms ● Resetting communication parameters to factory settings via EtherNet/IP The 3RW5 communication module supports the following additional features: ● I&M identification data 0 SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Description 3.4 Access options for the 3RW5 Soft Starter Access options for the 3RW5 Soft Starter ① SIRIUS 3RW5 Soft Starter (illustration similar) ② LED display on 3RW5 soft starter ③ EtherNet/IP (via 3RW5 EtherNet/IP communication module) ④ PC or programming device with configuration software of the controller, e.g.
Page 25
Possible number of applications per access path The following number of applications are simultaneously possible for each access path via the 3RW5 EtherNet/IP communication module: Access path Number of applications Programmable logic controller SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
V2.1 if the digital inputs have master control by activating the "Manual operation local - input controlled" bit in the process image output (PIQ). The PLC can regain master control at any time. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 27
Possible for 3RW50, 3RW52, 3RW55 and 3RW55 Failsafe Soft Starters. For 3RW55 Soft Starters as of firmware version V2.1, only if the input action "Operating mode manual - local" has been parameterized and activated. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 28
3RW5 HMI High Feature, control switches to "Manual - local - input controlled". Additional information Further information on the 3RW5 Soft Starters and restoring the factory settings of the device can be found in the Equipment Manual of the respective 3RW5 Soft Starter. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master Control > Release Control" Withdrawal of master control by other control sources In "Automatic" mode, control can be withdrawn by any control source. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 30
● Command in SIRIUS Soft Starter ES (TIA Portal) (local interface on the 3RW5 HMI High Feature) Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master Control > Get Control" SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 31
"Automatic" mode or alternatively to the Input IN or the digital inputs. Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel > Master Control > Release Control" SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 32
Further information on the operation of SIRIUS Soft Starter ES (TIA Portal) can be found in the online help of SIRIUS Soft Starter ES (TIA Portal). Messages about the mode You will find more information on messages in chapter Messages about the mode (Page 81). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Equipment Manual of the 3RW5 Soft Starter. ● Parameterization mode via key combination on the 3RW5 Soft Starter Further information on the parameterization mode can be found in the Equipment Manual of the respective 3RW5 soft starter. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 34
Additional information For more information, see Chapter Operating modes (Page 26). Further information on the 3RW5 Soft Starters can be found in the Equipment Manual of the respective 3RW5 Soft Starter. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Download SIRIUS Soft Starter ES (TIA Portal) can be downloaded on the 3RW5 topic page (https://support.industry.siemens.com/cs/ww/en/view/109747404) or via the following link (https://support.industry.siemens.com/cs/ww/en/ps/24231/dl). You will find further information on the SIRIUS Soft Starter ES (TIA Portal) software program and necessary versions and updates in Catalog IC 10 (https://support.industry.siemens.com/cs/ww/en/view/109747945) and on the...
Page 37
Parameter comparison Service data (maximum pointer, statistic data) Trace Access via PROFIBUS or PROFINET Teleservice via MPI Routing Bulk engineering (group function) The "Professional" variant corresponds to the "Premium" version of V15.1 SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Use on the 3RW50 soft starter The following accessories are needed for using the 3RW5 communication module on the 3RW50 soft starter: ● Push-in lugs for wall mounting (3ZY1311-0AA00) ● COM connecting cable (3RW5900-0CC00) SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
2. Mount the 3RW5 communication module (Page 42). Result You have mounted the 3RW5 communication module in the 3RW5 soft starter, which you can connect to the fieldbus (Page 55) via the 3RW5 communication module. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Deburr spots with sharp edges properly to prevent injuries. NOTICE Damage to property Hold the cover tight so that it does not fall into the interior. Ensure that no further foreign matter can get into the slot. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 41
3. Press the second part of the cover toward the interior of the device and break the cover inward at the preset breaking point. Result You can mount the 3RW5 communication module in the slot of the 3RW5 soft starter (Page 42). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Result You have mounted the 3RW5 communication module in the 3RW5 soft starter, which you can connect to the fieldbus (Page 55) via the 3RW5 communication module. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
NOTICE Damage to property due to electrical voltage Switch off the power to the 3RW5 soft starter before starting work (main and control supply voltage). Note A magnetic screwdriver simplifies disassembly. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 44
4. Pull the 3RW5 communication module out of the slot of the 3RW5 soft starter with your fingers. Result You have removed the 3RW5 communication module and can now mount another 3RW5 communication module. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
● 2 head screws M4 x 12 DIN ISO 7045 to fit the drill-holes ● Screwdriver (depending on the drive of the screws) ● 2 push-in lugs (accessories) for wall mounting (Page 38) Illustration similar SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 46
COM connecting cable to the 3RW50 soft starter (Page 49) and on the 3RW5 communication module (Page 51) and connect the 3RW50 soft starter to the fieldbus via the 3RW5 communication module (Page 55). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
1. Loosen the head screws on the 3RW5 communication module. 2. Pull out the push-in lugs from the 3RW5 communication module. Result You have removed the 3RW5 communication module and can now mount another 3RW5 communication module. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 48
Installing and removing 4.4 Removing the 3RW5 communication module from a level surface SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
● 3RW50 soft starter ● Removed hinged cover Further information on removing the hinged cover can be found in the Equipment Manual of the 3RW50 soft starter. ● COM connecting cable (accessory) SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 50
Result You have connected the COM connecting cable to the 3RW50 soft starter. You can connect the other side of the COM connecting cable to the 3RW5 communication module (Page 51). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Material damage due to incorrect plug-in connection Use the front plug-in connection of the 3RW5 communication module. The rear plug-in connection is not suitable for connecting to the COM connecting cable. Illustration similar SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 52
The 3RW5 communication module is now properly mounted and connected to the 3RW50 soft starter. You can connect the 3RW50 soft starter via the 3RW5 communication module on the fieldbus (Page 55). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
3RW5 communication module. Result You have disconnected the 3RW5 communication module from the 3RW50 soft starter. Place the cover cap onto the front plug-in connection of the 3RW5 communication module. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Further information on installing the hinged cover can be found in the Equipment Manual of the 3RW50 soft starter. Result You have disconnected the COM connecting cable from the 3RW50 soft starter. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Generally follow the instructions in the EMC Guide (http://www.siemens.com/emc-guideline) and implement the measures stated in it for shielding the cables and for connecting the shield.
Page 56
2. Secure the cable with a cable tie. Result The 3RW5 communication module is now properly mounted and connected. You can integrate the 3RW5 soft starter into the associated network environment. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
4. Pull the bus connector of the cable out of the socket of the 3RW5 communication module. Result You have disconnected the 3RW5 communication module from the bus connection. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
• 3RW5 soft starter, 3RW5 communication module, 3RW5 HMI High Feature • EDS file • SIRIUS Soft Starter ES (TIA Portal) You will find current downloads and a history of the versions with new features on the 3RW5 topic page (https://support.industry.siemens.com/cs/ww/en/view/109747404). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 60
Result The 3RW5 soft starter is integrated and parameterized as an adapter in the EtherNet/IP system. You can program the controller and commission the 3RW5 soft starter in the EtherNet/IP system. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
If parameter "IP address setting" (Page 67) is set to "Via parameter (IP address, subnet mask, router address)", the IP parameters can always be set via the local interface and on the 3RW5 HMI High Feature, even if no EtherNet/IP connection exists. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
(default) of the IP parameters are listed in Chapter TCP/IP Interface Object (Page 135). Note Configuration without DHCP If the assistance of a 3RW5 HMI High Feature is not available, communication must have already taken place via EtherNet/IP. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 63
③ EtherNet/IP ④ SIRIUS 3RW5 Soft Starter / adapter : Steps to be taken in the procedure 1. Integrate the 3RW5 Soft Starter in the configuration software of the controller with the EDS file as an adapter in the EtherNet/IP system (Page 69).
"Via parameter (IP address, subnet mask, router address)" Note IP address setting If parameter "IP address setting" (Page 67) is set to "Via BOOTP/DHCP server", you can only read out the IP parameters. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 65
② PC or programming device with configuration software of controller ③ EtherNet/IP ④ SIRIUS 3RW5 Soft Starter / adapter ⑤ PC with SIRIUS Soft Starter ES (TIA Portal) ⑥ 3RW5 HMI High Feature (accessories depend on 3RW5 soft starter) : Steps to be taken in the procedure 1.
DHCP messages. Note the settings in the configuration software of the controller. Note Set static IP parameters Static IP parameters that were previously set are overwritten and deleted by temporary IP parameters. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
3RW5 communication module using the MAC address (Page 67). Note Via BOOTP/DHCP server If parameter "IP address setting" is set to "Via BOOTP/DHCP server", the 3RW5 EtherNet/IP communication module restarts without a valid IP address and resends DHCP messages. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 68
You can only read out the IP parameters on the 3RW5 HMI High Feature, via the local interface on the 3RW5 HMI High Feature, and via the TCP/IP Interface Object (Page 135) (static IP parameter). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
3. Insert the 3RW5 soft starter in the EtherNet/IP system. Result The 3RW5 Soft Starter is integrated into the EtherNet/IP system as an adapter in the configuration software of the controller. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
"Control via digital input" (Page 33). Additional information You will find more information on restoring the factory setting on the device in the Equipment Manual of the 3RW52 soft starter. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
You will find more information on operating the 3RW5 HMI High Feature in the Equipment Manual of the 3RW5 Soft Starter. ● User program via the Dataset Object "Parameters" (Page 122) SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 72
Explanation in the following table. When making the settings via the 3RW5 HMI High Feature, observe the Equipment Manual of the 3RW5 soft starter. You can select the parameter set directly in the SIRIUS Soft Starter ES (TIA Portal). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 73
The following table describes the assignment of the substitute values "Parameter set bit 0" and "Parameter set bit 1": Parameter set Parameter set bit 0 Parameter set bit 1 Process image error Parameter set 1 (PS1) Parameter set 2 (PS2) Parameter set 3 (PS3) SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 74
Configuring 6.3 Operation on failure of the bus connection to the controller SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
– User program via the Dataset Object (Page 79) You will find faults and remedial measures for the 3RW5 communication module in Chapter Errors and remedial measures on the 3RW5 communication module (Page 80). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
3RW5 communication module (LED test). LED display on the 3RW5 EtherNet/IP communication module ① DIAG (red / green) ② BUS (red / green) ③ LINK (green) ④ No function SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Timeout of an exclusive owner connection: Control was stopped without connection termination. • Flashes red Interruption of the Ethernet communication. • Device has not yet received an IP address. • No supply voltage available. • SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 78
(e.g. Ethernet switch). Lights up green There is no Ethernet connection between the 3RW5 communication • module and a communication partner (e.g. Ethernet switch). No supply voltage available. • SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
The statistic data group together the operating states from the past that are relevant to the load. Depending on the 3RW5 soft starter, you can read out and evaluate the statistic data via the Dataset Object (Page 121). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Bus error Check the bus connection. • Check the bus parameters. • The error is acknowledged automatically • once it has been rectified. Visible on the display of the 3RW5 HMI Standard. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
3RW55 Soft Starters as of firmware version V2.1, only if the input action "Operating mode manual - local" has been parameterized and activated. For more information on setting the operating mode, see chapter Operating modes and master control function (Page 26). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 82
Messages and diagnosis 7.4 Messages about the mode SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
You need a 3RW5 HMI High Feature to update the firmware. The firmware cannot be updated via the fieldbus. Requirements ● Valid firmware update You will find the latest firmware files on the 3RW5 topic page (https://support.industry.siemens.com/cs/ww/en/view/109747404). ● 3RW5 HMI High Feature SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 84
Further information on the operation of SIRIUS Soft Starter ES (TIA Portal) can be found in the online help of SIRIUS Soft Starter ES (TIA Portal). Result You have performed a firmware update for the 3RW5 communication module. The 3RW5 communication module restarts automatically. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
You have performed a firmware update for the 3RW5 communication module using the Micro SD card. More information You will find more information on operating the 3RW5 HMI High Feature in the Equipment Manual of the 3RW5 soft starter. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
– 3RW52, 3RW55 and 3RW55 Failsafe soft starters: Mount the 3RW5 communication module in the 3RW5 soft starter (Page 42). 4. Connect the 3RW5 communication module to the bus connection (Page 55). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 87
Set the communication parameters anew. If you backed up the communication parameters to a micro SD card before replacement, you can transfer them from the micro SD card to the replacement device. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
The following procedures are possible via the 3RW5 communication module: Via the "Identity" object with the general "Reset" service and the "Factory settings" command (Reset with command 1) (Page 104). Only the communication parameters are reset here. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 89
3RW5 HMI High Feature or via the SIRIUS Soft Starter ES (TIA Portal) on the local interface on the 3RW5 HMI High Feature can be found in the 3RW5 Soft Starter Equipment Manual. Result The factory setting of the selected device or all devices is restored. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 90
Maintenance and service 8.3 Restoring factory setting SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Technical data in Siemens Industry Online Support Technical data sheet You can also find the technical data of the product at Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/16212/td). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key.
Page 92
Technical data 9.1 Technical data in Siemens Industry Online Support SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Dimension drawings 10.1 CAx data You can find the CAx data in the Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/16212/td). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key. 2. Click the "CAx data link.
10.2 Drilling patterns for 3RW5 communication module on the 3RW50 soft starter 10.2 Drilling patterns for 3RW5 communication module on the 3RW50 soft starter 3RW5 communication module on the 3RW50 soft starter size S6 SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 95
Dimension drawings 10.2 Drilling patterns for 3RW5 communication module on the 3RW50 soft starter 3RW5 communication module on the 3RW50 soft starter size S12 SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 96
Dimension drawings 10.2 Drilling patterns for 3RW5 communication module on the 3RW50 soft starter SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Circuit diagrams 11.1 CAx data You can find the CAx data in the Siemens Industry Online Support (https://support.industry.siemens.com/cs/ww/en/ps/16212/td). 1. Enter the full article number of the desired device in the "Product" field, and confirm with the Enter key. 2. Click the "CAx data link.
Page 98
Circuit diagrams 11.1 CAx data SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
● Phase currents I L1, I L2, I L3 (8-bit current format) ● Last tripping current (9-bit current format) You will find a complete overview of all measured values in chapter Measured values (Page 120). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
● Number of motor overload trips ● Number of starts motor CW ● Number of starts motor CCW You will find a complete overview of the statistic data in chapter Statistic data (Page 121). SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Appendix A.2 Byte arrangement Byte arrangement If data longer than one byte is saved, the bytes are arranged as follows ("little endian"): SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
3RW5 soft starter. In the case of a parameterization error, the object number of the faulty parameter is displayed in the Dataset Object "Soft starter diagnostics" (Page 114) under "Faulty parameter number". SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
See the table below Serial Number UDINT Bytes 3 to 6 of the MAC address Product Name SHORT_STRING - Character string length USINT 0x11 (17 characters) ASCII character string STRING 3RW59 ETHERNET IP SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 105
0 = No group fault 1 = Group fault Major Unrecoverable Fault Serious device fault, e.g. basic unit hardware fault: 0 = No device fault 1 = Device fault 12 ... 15 Reserved SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
A.6 Message Router Object Message Router Object The Message Router Object is a CIP-defined object. It does not possess any class or instance attributes, but simply transfers explicit messages to the relevant objects. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Revision UINT Max Instance UINT Number of Instance UINT Instance attributes Attribute ID Access Instance attribute Data type Value / comment Get / Set Data ARRAY of BYTE Data of instance SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 108
The following table describes the assignment of the process images "Parameter set bit 0" and "Parameter set bit 1": Parameter set Parameter set bit 0 Parameter set bit 1 Process image error Parameter set 1 (PS1) Parameter set 2 (PS2) Parameter set 3 (PS3) SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 109
You can parameterize the measured values for the 3RW55 and 3RW55 Failsafe soft starters. You will find more information in the Equipment Manual of the 3RW5 soft starter and in the Dataset Object "Parameters". An overview of the measured values can be found in the following table. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 110
Active power REAL Power factor L1...3 Supported by SIRIUS 3RW50 Soft Starter Supported by SIRIUS 3RW52 Soft Starter Supported by SIRIUS 3RW55 Soft Starter Supported by SIRIUS 3RW55 Failsafe Soft Starter SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Opens a connection (max. 511 bytes). 0x5B Large_Forward_Open Opens a connection (max. 550 bytes). Class attributes Attribute ID Access Class attribute Data type Revision UINT Max Instance UINT Number of Instance UINT SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 112
Number of queries to the service "Forward_Close" that were rejected for other reasons, such as invalid format. Get / Set Connection UINT Total number of connection timeouts occurring in Timeouts connections controlled by this Connection Manager. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
UINT Instance attributes Attribute ID Access Instance attribute Data type Value / comment 301 ... 25409 Get / Set Data ARRAY of BYTE Data of instance (depends on the attribute ID) SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
BOOL Temperature sensor wire break BOOL Temperature sensor short-circuit BOOL Thermal motor model overload BOOL Motor overload protection - shutoff BOOL Idle time active BOOL Cooling time active BOOL Safety-related shutoff SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 115
Self-test active BOOL Self-test error BOOL Factory settings restored UINT Faulty parameter number BOOL Preset unequal actual configuration BOOL Temperature sensor overload BOOL Temperature sensor wire break BOOL Temperature sensor short-circuit SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 116
Output 1 active BOOL Output 2 active BOOL Output 3 active BOOL Output 4 active BOOL Output 1 - Time active BOOL Output 2 - Time active BOOL Output 4 - Time active SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 117
(241 ... 242) BOOL New EX parameter values detected BOOL Ex release denied - wrong CRC 1545 BOOL Analog output underflow (243 ... 247) BOOL Analog output overflow BOOL Missing initialization after maintenance SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 118
Test with small load active BOOL Operating temperature too high BOOL Automatic parameterization active 1613 BOOL Starting time limit - maintenance (270) demanded exceeded BOOL Starting time limit - maintenance demanded undershot SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 119
Message type: Error (ER), warning (MT) or other message type (-) 3RW52 Soft Starter from firmware version V2.0 3RW55 soft starter from firmware version V2.0 3RW55 soft starter from firmware version V2.1 SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Data for service "Get_Attributes_All". The byte for the services "Get_Attributes_Single" is shown in square brackets "[...]". Supported by SIRIUS 3RW50 and 3RW52 Soft Starters Supported by SIRIUS Soft Starters 3RW55 and 3RW55 Failsafe SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Data for service "Get_Attributes_All". The byte for the services "Get_Attributes_Single" is shown in square brackets "[...]". Supported by SIRIUS 3RW50 Soft Starter from firmware version V1.0 and 3RW52 from firmware version V2.0 Supported by SIRIUS Soft Starters 3RW55 and 3RW55 Failsafe SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 133
The "Invalid parameter value" diagnosis is then reported in the Dataset Object "Soft Starter Diagnostics" (Page 114). You will find the dependencies of the parameters in the Equipment Manual of the 3RW5 soft starter. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Data for service "Get_Attributes_All". The data for the services "Get_Attributes_Single" and "Set_Attributes_Single" are shown in square brackets "[...]". Supported by 3RW5 HMI High Feature from firmware version V2.0 Default encoding 3RW5 HMI High Feature firmware version V3.0 or higher SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Supplies the contents of one attribute. 0x10 Set_Attributes_Single Changes the contents of an attribute. Class attributes Attribute ID Access Class attribute Data type Revision UINT Max Instance UINT Number of Instance UINT SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 136
Copy of the ARP message triggered by the IP 28 USINT address conflict. Get / Set Encapsulation UINT Length of inactivity in seconds before the TCP Inactivity Timeout connection or DTLS session is closed. (0 = Deactivated) SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 137
Characteristic of the IANA Protocol management. 1 = A change of the following configuration is impending: Characteristic of the IANA Protocol management. The device has to be restarted to accept the change. 10 ... 31 Reserved SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 138
(Page 67) are linked to each other so that they remain identical. DNS Enable 0 = Deactivated 1 = The device will adopt host names through the query of a DNS server. 5 ... 31 Reserved SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Supplies the contents of one attribute. 0x10 Set_Attributes_Single Changes the contents of an attribute. Class attributes Attribute ID Access Class attribute Data type Revision UINT Max Instance UINT Number of Instance UINT SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 140
2: Auto MDI-X (0 = Not supported, 1 = Supported) 3: Manual Speed/Duplex (0 = Not supported, 1 = Supported) 4 ... 31: Reserved Speed/Duplex Options STRUCT of See the table below SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 141
Speed in Mbps at which the interface is to • • • be operated USINT Interface Duplex Mode • • (only if autonegotiation is deactivated). Duplex mode of the interface: • 0 = Half duplex 1 = Full duplex SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 142
Appendix A.11 Ethernet Link Object SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
EDS file The properties of an EtherNet/IP device are described in an EDS file (EDS = Electronic Data Sheet) containing all the information required to integrate the device into an EtherNet/IP system. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 144
The MAC address can generally be read from the front of the device, e.g.: 08-00-06-6B-80-C0. Messages Data that is transferred from the 3RW5 soft starter and indicates the current operating status. Parameterization Parameterization is the definition of parameters using the parameterization software. SIRIUS 3RW5 EtherNet/IP communication module Equipment Manual, 03/2020, A5E45131885002A/RS-AB/002...
Page 145
Device which initiates a connection or a request. SIRIUS Soft Starter ES (TIA Portal) SIRIUS Soft Starter ES (TIA Portal) is the central software for commissioning, operating, and diagnostics of the SIRIUS 3RW5 Soft Starter series. Writing data Data are transferred to the 3RW5 soft starter.