Siemens PROFINET SIRIUS 3RW5 Equipment Manual page 176

Soft starters and solid-state switching devices
Hide thumbs Also See for PROFINET SIRIUS 3RW5:
Table of Contents

Advertisement

Appendix
A.4 Data sets
Byte
Data format Maximum pointer
16
Unsigned8
Maximum phase current I L1 (%)
17
Unsigned8
Phase current I L2 max (%)
18
Unsigned8
Phase current I L3 max (%)
20
Unsigned16
Maximum trigger current
22
Unsigned16
Number of motor overload trips
24
Signed32
Maximum trigger current
28
Signed32
Minimum phase current I L1 (rms)
32
Signed32
Phase current I L2 min (rms)
36
Signed32
Phase current I L3 min (rms)
40
Signed32
Maximum phase current I L1 (rms)
44
Signed32
Phase current I L2 max (rms)
48
Signed32
Phase current I L3 max (rms)
52
Unsigned16
Line-to-line voltage U L1-L2 min
54
Unsigned16
Line-to-line voltage U L2-L3 min
56
Unsigned16
Line-to-line voltage U L3-L1 min
58
Unsigned16
Line-to-line voltage U L1-L2 max
60
Unsigned16
Line-to-line voltage U L2-L3 max
62
Unsigned16
Line-to-line voltage U L3-L1 max
69
Unsigned8
Maximum switching element heating
70
Unsigned8
Minimum line frequency
71
Unsigned8
Maximum line frequency
72
Unsigned32
Operating hours - motor current = 18 ... 49.9% x Ie 0 ... 4 294 967 295 s
76
Unsigned32
Operating hours - motor current = 50 ... 89.9% x Ie 0 ... 4 294 967 295 s
80
Unsigned32
Operating hours - motor current = 90 ... 119.9% x
Ie
84
Unsigned32
Operating hours - motor current = 120 ... 1000% x
Ie
88
Unsigned32
Operating hours - device
96
Signed32
Starting current I max (rms)
100
Signed32
Starting current I L1 max (rms)
104
Signed32
Starting current I L2 max (rms)
108
Signed32
Starting current I L3 max (rms)
112
Unsigned16
Number of starts with ext. bypass
114 ...
-
Reserved
125
Supported by SIRIUS 3RW50 soft starter from firmware version V1.0 and 3RW52 from firmware version V2.0
1)
Supported by SIRIUS 3RW55 and 3RW55 Failsafe soft starters
2)
3RW55 soft starter from firmware version V2.0
3)
4)
Not supported by SIRIUS 3RW55 Failsafe soft starter
176
Value range
0 ... 796.9 %
0 ... 796.9 %
0 ... 796.9 %
0 ... 1 000 %
0 ... 65 535
-20 000 ... 20 000 A
-20 000 ... 20 000 A
-20 000 ... 20 000 A
-20 000 ... 20 000 A
-20 000 ... 20 000 A
-20 000 ... 20 000 A
-20 000 ... 20 000 A
0 ... 1 500 V
0 ... 1 500 V
0 ... 1 500 V
0 ... 1 500 V
0 ... 1 500 V
0 ... 1 500 V
0 ... 250 %
0 ... 100 Hz
0 ... 100 Hz
0 ... 4 294 967 295 s
0 ... 4 294 967 295 s
0 ... 4 294 967 295 s
-20 000 ... 20 000 A
-20 000 ... 20 000 A
-20 000 ... 20 000 A
-20 000 ... 20 000 A
0 ... 65 535
-
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
Incre‐
3RW
ment
50 /
55 /
52
55-F
1)
2)
3.125 % r
r
3.125 % r
r
3.125 % r
r
3.125 % r
r
1
r
r
0.01 A
r
r
0.01 A
r
r
0.01 A
r
r
0.01 A
r
r
0.01 A
r
r
0.01 A
r
r
0.01 A
r
r
0.1 V
-
r
0.1 V
-
r
0.1 V
-
r
0.1 V
-
r
0.1 V
-
r
0.1 V
-
r
1 %
r
r
0.5 Hz
-
r
0.5 Hz
-
r
1 s
r
r
1 s
r
r
1 s
r
r
1 s
r
r
1 s
r
r
0.01 A
r
r
0.01 A
r
r
0.01 A
r
r
0.01 A
r
r
1
r
r
3), 4)
-
-
-

Advertisement

Table of Contents
loading

Table of Contents