9.1.1

Performing firmware update with micro SD card (3RW5 HMI High Feature)

Requirements
• Micro SD card with valid firmware file (*.upd)
You will find more information and requirements for supporting the micro SD card in the
Equipment Manual of the 3RW5 soft starter.
• The valid firmware file is located in the root directory (topmost level).
• 3RW5 HMI High Feature
Menu "Micro SD card > FW update".
Procedure
Note
Access to micro SD card.
Please note that the micro SD card is inserted in the 3RW5 HMI High Feature during updating of
the firmware.
Premature removal of the micro SD card from the 3RW5 HMI High Feature is not permissible and
will terminate updating of the firmware. Data could also be lost.
1. Select the folder of the 3RW5 communication module.
2. Select the firmware file of the 3RW5 communication module and confirm with the OK button.
You can see the firmware update is being performed from the progress bar on the display.
Following successful updating of the firmware, the 3RW5 communication module restarts
automatically.
3. Check the new firmware version in the "Overview" menu.
Result
You have performed a firmware update for the 3RW5 communication module using the Micro SD
card.
More information
You will find more information on operating the 3RW5 HMI High Feature in the Equipment
Manual of the 3RW5 soft starter.
9.2

Replacing the 3RW5 communication module

Communication parameters are stored in the 3RW5 communication module and not
automatically transferred into the replacement device.
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004
9.2 Replacing the 3RW5 communication module
Maintenance and service