Perform The Firmware Update Using Micro Sd Memory Card (3Rw5 Hmi High Feature) - Siemens SIRIUS 3RW5 series Manual

Soft starters and solid-state switching devices modbus tcp communication module
Hide thumbs Also See for SIRIUS 3RW5 series:
Table of Contents

Advertisement

Maintenance and service
8.1 Firmware update
8.1.1
Perform the firmware update using micro SD memory card
(3RW5 HMI High Feature)
Requirements
● Micro SD memory card with valid firmware file (*.udp)
● You are in menu "Memory Card > FW Update"
Procedure
Note
Access to micro SD memory card.
Please note that the micro SD memory card is in the 3RW5 HMI High Feature during
updating of the firmware.
Premature removal of the micro SD memory card from the 3RW5 HMI High Feature is not
permissible and will terminate updating of the firmware. Data could also be lost.
1. Select the folder of the respective device.
2. Select the firmware file of the device and confirm with "OK".
You can see the firmware update is being performed from the progress bar on the
display.
Following successful updating of the firmware, the respective device then restarts
automatically.
3. Check the new firmware version in the "Overview" menu.
Result
You have performed a firmware update for the selected device using the micro SD memory
card. The firmware update is documented in the device logbook.
More information
You will find more information on operating the 3RW5 HMI High Feature in the Manual of the
3RW5 soft starter.
64
SIRIUS 3RW5 Modbus TCP communication module
Manual, 03/2018, A5E43676481002A/RS-AA/001

Advertisement

Table of Contents
loading

Table of Contents