7 Programming FCs (Functions) and FBs for S7 Ethernet CPs
FC 12 PNIO_RECV - continued
Table 7-12 Condition Codes PNIO_RECV, continued
NDR
ERROR
STATUS
0
1
8F31
0
1
8F32
0
1
8F3A
0
1
8F42
0
1
8F43
0
1
8F44
0
1
8F45
0
1
8F7F
0
1
8090
0
1
80A0
0
1
80A1
0
1
80B0
0
1
80B1
0
1
80C0
0
1
80C1
0
1
80C2
0
1
80C3
0
1
80C4
7.8.3
General Response of the FCs for PROFINET IO
IO Consumer Status (IOCS) and IO Provider Status (IOPS)
The two communication partners - CPU/CP on the one hand and IO device on the
other - both have status information for the data (GOOD or BAD). This status
information is transferred parallel to the data. The status of the partner that sends
the data is called IOPS (IO Provider Status), the status of the receiving partner is
called IOCS (IO Consumer Status).
The IOPS and IOCS status are not necessarily identical. It is, for example,
possible that the S7-300 CPU is in STOP mode (output disable or no PROFINET
IO blocks active). In this case, the CP as PROFINET IO controller transfers the
BAD status to the IO devices.
A -248
Parameter is in the write-protected 2nd act. data block.
H
Parameter contains a DB number that is too high.
H
Destination area is not loaded (DB).
H
Timeout reading a parameter from the I/O area.
H
Timeout writing a parameter to the I/O area.
H
Address of the parameter to be read is disabled in the accessed rack.
H
Address of the parameter to be written is disabled in the accessed rack.
H
Internal error, e.g. illegal ANY reference.
H
Module with this address does not exist.
H
Negative acknowledgment reading from the module.
H
Negative acknowledgment writing to the module.
H
The module does not recognize the data record.
H
S
The specified data record length is wrong.
H
or
S
The CP changes to STOP.
The data record cannot be read.
H
The specified data record is currently being processed.
H
There are too many jobs pending.
H
Resources occupied (memory).
H
Communication error: (occurs temporarily and a repetition in the user
H
program will often remedy the problem).
S7-CPs for Industrial Ethernet Configuring and Commissioning
Meaning
C79000-G8976-C182-07