Siemens SIMATIC NET S7-300 Manual page 230

Cps for industrial ethernet
Hide thumbs Also See for SIMATIC NET S7-300:
Table of Contents

Advertisement

7 Programming FCs (Functions) and FBs for S7 Ethernet CPs
FB55 IP_CONFIG - continued
Table 7-9
Condition Codes for FB55 IP_CONFIG, Fortsetzung
DONE
ERROR
Errors detected in the evaluation of the FB in the CPU or on the interface between CPU and CP.
0
1
0
1
0
1
0
1
0
1
Further errors detected on the interface between the CPU and CP.
0
1
0
1
0
1
0
1
0
1
0
1
Errors detected when evaluating the FB on the CP.
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
A -230
STATUS
8183
The CP rejects the requested data record number.
H
8184
System error or illegal parameter type<F 9>. (data type of the ANY
H
pointer CONF_DB not OK)
(Currently only the byte data type is accepted)
8185
The value of the LEN parameter is larger than the CONF_DB less the
H
reserved header (4 bytes) or the length information is incorrect.
8186
Illegal parameter detected
H
The ANY pointer CONF_DB does not point to a data block.
8187
Illegal status of the FB
H
Data in the header of CONF_DB was possibly overwritten.
8A01
The status code in the data record is invalid (value is >= 3).
H
8A02
There is no job running on the CP; the FB, however, expected an
H
acknowledgment for a completed job.
8A03
There is no job running on the CP and the CP is not ready; the FB
H
triggered the first job to read a data record.
8A04
There is no job running on the CP and the CP is not ready; the FB
H
nevertheless expected an acknowledgment for a completed job.
8A05
There is a job running, but there was no acknowledgment; the FB
H
nevertheless triggered the first job for a read data record job.
8A06
A job is complete but the FB nevertheless triggered the first job for a
H
read data record job.
8B01
Communication error
H
The DB could not be transferred
8B02
Parameter error
H
Double parameter field
8B03
Parameter error
H
The subfield in the parameter field is not permitted.
8B04
Parameter error
H
The length specified in the FB does not match the length of the
parameter fields / subfields.
8B05
Parameter error
H
The length of the parameter field is invalid.
8B06
Parameter error
H
The length of the subfield is invalid.
8B07
Parameter error
H
The ID of the parameter field is invalid.
8B08
Parameter error
H
The ID of the subfield is invalid.
8B09
System error
H
The connection does not exist
Meaning
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07