Table 7-11 Condition Codes PNIO_SEND, Fortsetzung
DONE
ERROR
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07
7 Programming FCs (Functions) and FBs for S7 Ethernet CPs
FC11 PNIO_SEND - continued
STATUS
8F31
Parameter is in the write-protected 2nd act. data block.
H
8F32
Parameter contains a DB number that is too high.
H
8F3A
Destination area is not loaded (DB).
H
8F42
Timeout reading a parameter from the I/O area.
H
8F43
Timeout writing a parameter to the I/O area.
H
8F44
Address of the parameter to be read is disabled in the accessed
H
rack.
8F45
Address of the parameter to be written is disabled in the
H
accessed rack.
8F7F
Internal error, e.g. illegal ANY reference.
H
8090
Module with this address does not exist.
H
80A0
Negative acknowledgment reading from the module.
H
80A1
Negative acknowledgment writing to the module.
H
80B0
The module does not recognize the data record.
H
S
80B1
The specified data record length is wrong.
H
or
S
The CP changes to STOP.
80C0
The data record cannot be read.
H
80C1
The specified data record is currently being processed.
H
80C2
There are too many jobs pending.
H
80C3
Resources occupied (memory).
H
80C4
Communication error: (occurs temporarily and a repetition in the
H
user program will often remedy the problem).
Meaning