SIMATIC CP 4163-1 Preface Properties and functions SIMATIC NET LEDs, connections, QR code Installation, connection, commissioning, removal S7-4100 - Industrial Ethernet SIMATIC CP 4163-1 Configuration Diagnostics and maintenance Operating Instructions Technical specifications Approvals Dimension drawings Bibliography 12/2022 C79000-G8976-C588-01...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Preface Validity This description contains information on the following product: • CP 4163-1 Article number 6DL4163-1EX00-0XE0 Hardware product version 1 Firmware version V1.0 Communications processor for SIMATIC S7-4100 The CP has a PN/IE interface for connection of the SIMATIC S7-4100 to PROFINET IO/Industrial Ethernet.
Page 4
/2/ (Page 49) • Knowledge of engineering with SIMATIC PCS neo Current manual edition on the Internet You will also find the current version of this manual on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15334/man) SIMATIC CP 4163-1...
Page 5
Preface Abbreviations and terminology Term Synonyms Notices Communications processor The term "CP" is used in this document in place of the full product name SIMATIC CP 4163-1. If not otherwise specified, applies to the module and to the module function. Central processing unit If not otherwise specified, applies to the module and to the module function.
Page 6
Observe the PCS neo security concept, see: Link: (https://support.industry.siemens.com/cs/ww/en/view/109802560) Device defective If a fault develops, please send the device to your Siemens representative for repair. Repairs on-site are not possible. Decommissioning Shut down the device properly to prevent unauthorized persons from accessing confidential data in the device memory.
Page 7
Siemens contact. Keep to the local regulations. You will find information on returning the product on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/view/109479891) SIMATIC NET glossary The SIMATIC NET glossary describes terms that may be used in this document.
Table of contents Preface ..............................3 Properties and functions........................11 Application ........................11 Communication services ....................11 Further services and characteristics ..................12 Configuration limits and performance data................. 13 1.4.1 Rack components....................... 13 1.4.2 PROFINET IO characteristic data ..................13 1.4.3 Characteristic data Open User Communication ..............
Page 10
Table of contents Maintenance ........................37 5.2.1 Update firmware........................ 37 5.2.2 Replacing a module without a programming device ............38 5.2.3 Resetting to factory settings ....................38 Technical specifications........................39 Technical specifications of the CP 4163-1 ................39 Assignment of the PN/IE interfaces ..................40 Permitted cable lengths - Ethernet ..................
Properties and functions Application Automation system The CP 4163-1 communications processor is intended for operation in the SIMATIC S7-4100 system. The CP enables an additional connection of the SIMATIC S7-4100 to Industrial Ethernet and PROFINET. The CP has the following interface: •...
Properties and functions 1.3 Further services and characteristics Further services and characteristics • Media redundancy Within an Ethernet network with a ring topology, the CP supports the media redundancy protocol (MRP). You can assign the role of media redundancy manager and client to the •...
Properties and functions 1.4 Configuration limits and performance data Configuration limits and performance data 1.4.1 Rack components Use of multiple CPs By operating several CPs, you can increase the configuration limits listed below for the station as a whole. The CPU does, however, have set limits for the entire configuration. Observe the information in the documentation of the CPU, see /3/ (Page 49).
Properties and functions 1.4 Configuration limits and performance data 1.4.3 Characteristic data Open User Communication Open User Communication (OUC) provides access to communication over TCP, ISO-on-TCP and UDP connections. Characteristic Explanation / values Number of connections • Max. number of connections via T blocks: (ISO-on-TCP + TCP + UDP) ≤...
Keep the firmware version of the communications modules up to date Check regularly for security updates of the firmware and use them. Information regarding product news and new firmware versions is available at the following address: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15334/dl) 1.5.2 Software requirements - Configuration Software for configuration and online functions...
Page 16
Properties and functions 1.5 Requirements for use SIMATIC CP 4163-1 Operating Instructions, 12/2022, C79000-G8976-C588-01...
LEDs, connections, QR code LEDs ① Status displays of the CP (always visible) ② LEDs (under the front panel of the CP) Meaning of the LED displays CP 4163-1 has the following three LEDs to display the current operating status and the diagnostics status: •...
Page 18
LEDs, connections, QR code 2.1 LEDs Table 2- 1 Meaning of the LED symbols LED pattern Meaning LED is off. LED lights up LED flashes LED flickers. LED state is irrelevant. Table 2- 2 Meaning of the LED displays LED (green) LED (red) LED (yellow) Meaning...
LEDs, connections, QR code 2.2 PN/IE interface The following table shows the meaning of the various color combinations of the LEDs X1 P1 R and X1 P2 R. Table 2- 3 Meaning of the LEDs LED (green) LED (yellow) Meaning •...
LEDs, connections, QR code 2.3 Connections on the slot and module MAC addresses The CP is supplied with three default MAC addresses with the following assignment: • PN/IE interface: The MAC address of the PROFINET interface is printed on the housing (visible in the engineering at "Accessible devices in the subnet") •...
Page 21
The QR code is simultaneously an Identification Link in accordance with IEC 61406-1. When you scan the QR code (e.g. with a smartphone), you directly open the Siemens Internet page of the digital nameplate. Digital nameplate The digital nameplate is: •...
Page 22
LEDs, connections, QR code 2.4 QR code SIMATIC CP 4163-1 Operating Instructions, 12/2022, C79000-G8976-C588-01...
Installation, connection, commissioning, removal Safety notices on the use of the device Note the following safety notices when setting up and operating the device and during all associated work such as installation, connecting up or replacing the device. Important notes on using the device WARNING Safety requirements for installation The devices are "open equipment"...
Installation, connection, commissioning, removal 3.1 Important notes on using the device WARNING The device may only be operated in an environment with pollution degree 1 or 2 as described in EN/IEC 60664-1, GB/T 16935.1. WARNING Power supply The device is designed for operation with a directly connectable safety extra low voltage (SELV) from a limited power source (LPS).
Installation, connection, commissioning, removal 3.1 Important notes on using the device WARNING Transient overvoltages Take measures to prevent transient overvoltages of more than 40% of the rated voltage (or more than 119 V). This is the case if you only operate devices with SELV (safety extra-low voltage).
Installation, connection, commissioning, removal 3.2 Installation, removal and repairs in hazardous areas Installation, removal and repairs in hazardous areas WARNING Impermissible accessories and spare parts Risk of explosion in hazardous areas • Only use original accessories and original spare parts. •...
• Observe the device approvals applicable for your country. WARNING Unauthorized repair of devices in explosion-proof design Risk of explosion in hazardous areas • Repair work may only be performed by personnel authorized by Siemens. Installing and connecting NOTICE Improper mounting Improper mounting may damage the device or impair its operation.
Installation, connection, commissioning, removal 3.3 Installing and connecting Installation and connecting NOTICE Read the SIMATIC S7-4100, Controller system manual Prior to installation, connecting and commissioning, read the corresponding sections in the "SIMATIC S7-4100, Controller system manual"; see /2/ (Page 49). You will also find information on the permitted slots of CPs here.
Installation, connection, commissioning, removal 3.4 Commissioning Contacts of the bus module WARNING Dangerous system conditions • Access to the contact of a bus module, a U-connector or a module is impermissible. When a bus module is used, unused slots must be protected by slot covers. •...
Installation, connection, commissioning, removal 3.5 Disassembly Disassembly WARNING Improper disassembly Improper disassembly may result in a risk of explosion in hazardous areas. For proper disassembly, observe the following: • Before starting work, ensure that the electricity is switched off. • Secure remaining connections so that no damage can occur as a result of disassembly if the system is accidentally started up.
• Do not connect the device directly to the Internet. Operate the device within a protected network area. • Check regularly for news on the Siemens Internet pages. – You can find information on Industrial Security here: Link: (https://www.siemens.com/industrialsecurity) –...
Page 32
Configuration 4.1 Security recommendations Passwords • Define rules for the use of devices and assignment of passwords. • Regularly update the passwords to increase security. • Only use passwords with a high password strength. Avoid weak passwords for example "password1", "123456789" or similar. •...
Configuration 4.2 CP in the configuration Table 4- 1 Server ports of the CP Protocol / Port number Default of the Port status Authentication function (protocol) port S7 communication 102 (TCP) Open Open SNMP 161 (UDP) Closed Open after configuration PROFINET 34962 / 34963 / Open...
Configuration 4.3 Creating and configuring a CP Creating and configuring a CP Requirement • The station for which the CP is intended has been created. • The address parameters and the values of the other CP parameters are known. • "Navigation area" > "Devices" > "Hierarchical hardware engineering" is open. Creating a CP 1.
Diagnostics and maintenance Diagnostics 5.1.1 Diagnostics options Diagnostics options You have the following diagnostics options available for the module: • The LEDs of the module For information on the LED displays, refer to the section LEDs (Page 17). • Engineering: Diagnostic functions in the "Online and diagnostics" menu Here, you can obtain information on the selected module: –...
Page 36
The information on the properties of SNMP-compliant devices is entered in MIB files (MIB = Management Information Base). You will find detailed information on SNMP and the Siemens Automation MIB in the manual "Diagnostics and Configuration with SNMP" that you will find on the Internet: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15334/man)
Update firmware New firmware versions of the CP If a new firmware version is available for the CP, you will find this on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15334/dl) Save the firmware file on your server PC.
Diagnostics and maintenance 5.2 Maintenance 5.2.2 Replacing a module without a programming device General procedure The configuration data of the CP is stored on the CPU. This makes it possible to replace this module with a module of the same type (identical article number) without an engineering station.
Technical specifications Technical specifications of the CP 4163-1 Note the information in the S7-4100 system manual /2/ (Page 49). In addition to the information in the system manual, the following technical specifications apply to the module. Table 6- 1 Technical specifications of the CP 4163-1 Technical specifications Article number 6DL4163-1EX00-0XE0...
Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180 • Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet See also Siemens Mall: (https://mall.industry.siemens.com) SIMATIC CP 4163-1 Operating Instructions, 12/2022, C79000-G8976-C588-01...
You will find the declarations of conformity listed below and certificates of the product on the Internet at the following address: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15334/cert) You can view the considered standards in the respective certificate which is available on the Internet at the address listed above.
Page 42
Directive of the European Parliament and of the Council of 8 June 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment UK Declaration of Conformity Importer UK: Siemens plc Sir William Siemens House Princess Road Manchester M20 2UR The product meets the requirements of the following directives: •...
Page 43
• EN IEC 60079-0 - Explosive atmospheres - Part 0: Equipment - General requirements • EN 60079-7 - Explosive Atmospheres - Part 7: Equipment protection by increased safety 'e' Importer UK: Siemens plc (see above) Classification: Ex na IIC T4 Gc The product meets the requirements of the following standards: •...
Page 44
Approvals The CP meets the requirements of the following directives: • EU directive 2014/30/EU "Electromagnetic Compatibility" (EMC directive) • EMC Regulations SI 2016/1091 The Electromagnetic Compatibility Regulations 2016 Applied standards: • EN 61000-6-2 Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for industrial environments •...
Page 45
Approvals Ta: Refer to the temperature class on the type plate of the CP Report / UL file: E223122 (NRAG, NRAG7) Note the conditions for the safe deployment of the product according to the section Notes on use in hazardous areas according to UL HazLoc and FM (Page 25). CSA Certification Mark Canadian Standard Association (CSA) nach Standard C 22.2 No.
Page 46
SIMATIC NET products are regularly submitted to the relevant authorities and approval centers for approvals relating to specific markets and applications. If you require a list of the current approvals for individual devices, consult your Siemens contact or check the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15334/dl)
Dimension drawings All dimensions in the dimension drawings are in millimeters. Figure B-1 Front view SIMATIC CP 4163-1 Operating Instructions, 12/2022, C79000-G8976-C588-01...