Note
For entries coded with 8Fxx
Standard and System Functions reference manual. The chapter describing error
evaluation with the RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the
properties dialog of the FC described here in the "Calls" tab.
Table 7-2
AG_SEND / AG_LSEND Codes
DONE
ERROR
1
0
0
0
0
0
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07
7 Programming FCs (Functions) and FBs for S7 Ethernet CPs
FC5 AG_SEND / FC50 AG_LSEND - continued
in STATUS, refer to the information in the STEP 7
H
STATUS
0000
Job completed without error.
H
0000
No job being executed.
H
8181
Job active.
H
7000
This code is possible only with the S7-300: the FC was called
H
with ACT=0; the job has not yet been processed.
8183
No configuration or the ISO/TCP service has not yet started on
H
the Ethernet CP.
S
8184
Illegal type specified for the SEND parameter.
H
S
System error (the source data area is incorrect).
8185
LEN parameter longer than SEND source area.
H
8186
ID parameter invalid.
H
S
ID != 1,2....16 (S7-300).
S
ID != 1,2....64.(S7-400)
8302
No receive resources on the destination station; the receiving
H
station cannot process received data quickly enough or has not
prepared any receive resources.
8304
The connection is not established. The send job should only be
H
attempted again after waiting for at least 100 ms.
8311
The destination station cannot be obtained under the specified
H
Ethernet address.
8312
Ethernet error on the CP.
H
8F22
Source area invalid, for example:
H
Area does not exist in the DB
LEN parameter < 0
8F24
Area error reading a parameter.
H
8F28
Alignment error reading a parameter.
H
8F32
Parameter contains a DB number that is too high.
H
8F33
DB number error.
H
8F3A
Area not loaded (DB).
H
8F42
Timeout reading a parameter from the I/O area.
H
Meaning