6 Programmed Communication Connections
6.5.4
Parameter Field for an E-Mail Connection
Meaning
To send E-mails, you must always set up one E-mail connection per IT-CP. The
E-mail connection specifies the mail server, over which all the E-mails sent by the
IT-CP are delivered.
You will find a detailed description of how to use the E-mail function with IT-CPs in
/5/.
Structure
Usable Subfields
Table 6-8
Subfield
ID
1
SUB_IP_V4
3
SUB_DNS_NAME
13
SUB_EMAIL_SENDER
18
SUB_CONNECT_NAME
A -174
Type = 4
ID = connection ID
No_of_subfields = n
Subfield 1
Subfield 2
Subfield n
*)
Type
(Please refer also to the general
description in Table 6-10 Page A -177)
IP address of the mail server, over which
the E-mails are sent.
The IP address can be specified in
absolute or symbolic form.
The symbolic form assumes that the IT-CP
knows the address of the domain name
server (DNS). This must be entered during
configuration of the IT-CP in HW Config, for
more detailed information, refer to the
online help of HW Config.
DNS name of the E-mail server
E-mail address of the sender
-
S7-CPs for Industrial Ethernet Configuring and Commissioning
Identifier for the connection type
Freely assignable connection reference;
must be specified in AG_SEND.
Range of values for the connection ID:
S
S7-400: 1,2 through 64
S
S7-300: 1,2 through 16
Parameter
Special Features / Notes
Use
( mandatory
/ optional)
**)
m / o
**)
m / o
m
o
Release 01/2007