7 Programming FCs (Functions) and FBs for S7 Ethernet CPs
FC5 AG_SEND / FC50 AG_LSEND - continued
Table 7-2
AG_SEND / AG_LSEND Codes
DONE
ERROR
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
A -200
STATUS
8F44
Address of the parameter to be read is disabled in the accessed
H
rack.
8F7F
Internal error, e.g. illegal ANY reference.
H
e.g. parameter LEN=0
S
8090
Module with this module base address does not exist.
H
S
The FC used does not match the system family being used
(different FCs must be used for S7 -300 and S7 -400).
8091
Logical base address not at a double word boundary.
H
8092
In the ANY reference, a type other than BYTE is specified.
H
(S7-400 only)
80A4
The communication bus connection between the CPU and CP is
H
not established. (Only with newer CPU versions)
80B0
The module does not recognize the data record.
H
80B1
The specified length (in the LEN parameter) is incorrect.
H
80B2
The communication bus connection between the CPU and CP is
H
not established.
80C0
The data record cannot be read.
H
80C1
The specified data record is currently being processed.
H
80C2
There are too many jobs pending.
H
80C3
CPU resources (memory) occupied.
H
80C4
Communication error (occurs temporarily and a repetition in the
H
user program will often remedy the problem).
80D2
Module base address incorrect.
H
Meaning
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07