Siemens SIMATIC NET S7-300 Manual page 235

Cps for industrial ethernet
Hide thumbs Also See for SIMATIC NET S7-300:
Table of Contents

Advertisement

Table 7-10 Codes for PN_InOut (FB88) and PN_InOut_Fast (FB90), Fortsetzung
DONE
ERROR
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
S7-CPs for Industrial Ethernet Configuring and Commissioning
Release 01/2007
C79000-G8976-C182-07
7 Programming FCs (Functions) and FBs for S7 Ethernet CPs
FB88 PN_InOut / FB90 PN_InOut_Fast - continued
STATUS
8090
(S7-400 only)
H
Parameter assignment error
An incorrect module address was specified; the address points to
an empty slot.
Note (only with FB90):
In the following cases, the value 8181
active); In actual fact, there is no communication:
S
The address points to a slot that contains a different module
type.
S
The addressed module is configured for PROFINET CBA
operation.
80A1
(only with FB90)
H
Possible communications errors:
S
Station-internal connection to addressed module being
terminated;
S
The configuration limits for connections of the CPU has been
exceeded;
S
The interface is being reinitialized.
80B0
(S7-300 only)
H
Block error: The data record number is wrong.
This status can also occur after the following actions:
S
Cold or warm restart after power DOWN/UP
S
Cold or warm restart on the CPU
80B1
(S7-300 only)
H
Block error: Data record length or offset wrong.
80B3
(S7-300 only)
H
Parameter error: Wrong CP address.
80C1
(S7-300 only)
H
Temporary error: The specified data record is currently being
processed.
80C2
(S7-300 only)
H
Temporary error: There is a job bottleneck; the data record cannot
be read yet.
80C3
(S7-300 only)
H
Temporary error: Resources (memory) in use.
80C4
(S7-300 only)
H
Communication error: occurs temporarily and a repetition in the
user program will often remedy the problem.
80D0
(S7-300 only)
H
Configuration error:
The maximum number of blocks of input and output data has
been exceeded; the interface DB is too large.
Meaning
is shown in STATUS (job
H
A -235