Checklist for General CP Functions

Table 8-5
Checklist for Typical Problems When Operating a CP in a System
Problem
The Ethernet CP will not
change to the RUN mode.
A -280
Possible Cause
Invalid configuration
loaded on the Ethernet
CP.
Switch set to STOP on the
Ethernet CP.
S7-CPs for Industrial Ethernet Configuring and Commissioning
Identifying the Cause and Remedy
Yellow STOP LED and red SF LED lit
continuously.
Call up the diagnostic buffer in NCM S7
Ethernet Diagnostics.
Example of an entry
CP STOP due to invalid CP parameter
assignment
What to do:
Correct the configuration of the Ethernet CP.
Query the operating mode in NCM S7
Diagnostics.
Operating mode: STOP, Cause: switch set to
STOP
What to do:
Change the switch to RUN on the Ethernet CP