5.7.2

External Peripherals

A) Angle / Lenght and ATB interface circuit board errors
The i3500 system can support up to 5 angle/length interfaces. Activation of
every angle sensor is done in the calibration menu section ''Enable/Disable
I/O''.
Error message
Angle sensor x defective # The angle sensor value in
Length x out of range #
Angle x is in Pre-calib.
Angle/length Comm #
Length x Not calibrated
Angle Not calibrated
Angle/length x Dr+
Telescopic Cranes Pressure Sensing
Execution process
volts is not valid (if < 1 volt
or > 4 volts).
A 0xFFFF code is sent by
angle/length card to indicate
that length sensor is not
present.
Indicates that angle/length
card is in pre-calibration
mode.
The i3500 system does not
receive data from angle sensor.
If ''time out'' delay is reached,
then a communication error
is displayed.
The 5 volts reference voltage
is not valid (if < 4.5 volts or
5.5 volts).
59
i3500 Troubleshooting
Cause of error
1) The Accelerometer or the
12 bits converter is
defective.
1) The Length sensor is not
installed
2) A wire is cut between
length sensor and circuit
board.
1) In operation mode, the
jumper must be taken out
from 'Cal' jumper located
on the circuit board.
2) Verify that calibration
value in bits of the
accelerometer is valid.
1) The angle/length circuit
board is defective,
2) The Can bus network
cable is broken.
Length sensor is not
calibrated.
Angle sensor is not
calibrated.
1) The Angle/length circuit
board is defective.
Instruction Manual