Festo CPX-CEC Series Manual page 35

Modular valve terminal with integrated controller codesys
Table of Contents

Advertisement

Figure: Setting the cyclic communication data
Only POS is supported in the cyclic communication data.
5. FCT settings for SoftMotion
The table below lists the FCT settings for SoftMotion, differentiated according to all drive controllers
supported.
FCT setting
CMMP
Control interface
CANopen
type
CAN address/node
Set using FCT
number
Bit rate
125 kBaud,
250 kBaud,
500 kBaud or
1 MBaud
Protocol/data profile
DS402
Factor group
Not used
Supply voltage
Internal only
Carrying out configuration
External access must be activated for synchronisation with SoftMotion:
1.
Open the "MotionTask" area in the task configuration.
2.
Activate the event type "triggered by external event".
3.
Select "CANopen_SYNC" as the event.
4.
Make sure that the priority of the MotionTask is set to a RealTime priority.
Figure: Task configuration
Modular valve terminal with integrated controller CPX-CEC-...
CMMS-ST
CMMS-AS
CMMD-AS
CANopen
Set using DIL
switch
125 kBaud,
250 kBaud,
500 kBaud or
1 MBaud
set using DIL switch
DS402
Not used
Internal only
SFC-LAC
SFC-LACI
CANopen
Set using FCT
125 kBaud,
250 kBaud,
500 kBaud or
1 MBaud
DS402
Internal or external
33