GD200A series VFD
Function
Name
code
Sampling cycle
P09.07
(T)
PID control
P09.08
deviation limit
Output upper
P09.09
limit of PID
Output lower
P09.10
limit of PID
Feedback
P09.11
offline detection
value
Feedback
P09.12
offline detection
time
Description
adjusting.
Setting range: 0.00–10.00s
This parameter means the sampling cycle of the
feedback. The modulator calculates in each
sampling cycle. The longer the sapling cycle is,
the slower the response is.
Setting range: 0.000–10.000s
The output of PID system is relative to the
maximum deviation of the close loop reference. As
shown in the diagram below, PID adjustor stops to
work during the deviation limit. Set the function
properly to adjust the accuracy and stability of the
system.
Reference value
Output frequency
Setting range: 0.0–100.0%
These parameters are used to set the upper and
lower limit of the PID adjustor output.
100.0 % corresponds to max. frequency or the
max. voltage of (P04.31)
Setting range of P09.09: P09.10–100.0%
Setting range of P09.10:
Set the PID feedback offline detection value, when
the detection value is smaller than or equal to the
feedback offline detection value, and the lasting
time exceeds the set value in P09.12, the VFD will
report "PID feedback offline fault" and the keypad
will display PIDE.
-83-
Feedback value
Bias limit
T
T
-100.0%–P09.09
Function parameters
Default
Modify
value
○
0.100s
○
0.0%
○
100.0%
○
0.0%
○
0.0%
○
1.0s
Need help?
Do you have a question about the Goodrive200A Series and is the answer not in the manual?
Questions and answers
Ou2 fault
An Ou2 fault on the INVT Goodrive200A Series indicates an IGBT Ph-V fault. Possible causes include:
- IGBT module fault
- Misoperation caused by interference
- Poor connection of driving wires
- Improper grounding
To fix it:
- Increase the acceleration time
- Change the power unit
- Check the driving wires
- Inspect external equipment and eliminate interference
- Ensure proper grounding