GD200A series VFD
Function
Name
code
Jumping
P08.11
frequency 2
Jumping
P08.12
frequency
range 2
Jumping
P08.13
frequency 3
Jumping
P08.14
frequency
range 3
P08.15 Traverse range This function applies to the industries where
Sudden
jumping
P08.16
frequency
range
Traverse boost
P08.17
time
Traverse
P08.18
declining time
Description
can set three jumping frequency. But this function
will be invalid if all jumping points are 0.
Set frequency f
Jump
frequency 3
Jump
frequency 2
Jump
frequency 1
Setting range: 0.00Hz –P00.03 (the max.
frequency)
traverse and convolution function are required
such as textile and chemical fiber.
The traverse function means that the output
frequency of the VFD is fluctuated with the set
frequency as its center. The route of the running
frequency is illustrated as below, of which the
traverse is set by
P08.15
as 0, the traverse is 0 with no function.
Output frequency
Jumping frequency
Center
frequency
Lower limit of
wobble frequency
Accelerate
Fall time of
wobble frequency
Traverse range: The traverse running is limited by
upper and low frequency.
The traverse range relative to the center
frequency: traverse range AW = center
frequency×traverse range P08.15.
Sudden jumping frequency = traverse range
AW×sudden jumping frequency range P08.16.
When run at the traverse frequency, the value
which is relative to the sudden jumping frequency.
The raising time of the traverse frequency: The
time from the lowest point to the highest one.
The declining time of the traverse frequency: The
-74-
1/2*Jump
frequency range 3
1/2*Jump
frequency range 3
1/2*Jump
frequency range 2
1/2*Jump
frequency range 2
1/2*Jump
frequency range 1
1/2*Jump
frequency range 1
Time t
and when
P08.15
is set
Wobble frequency amplitude
Decelerate per
dec. time
Rise time of
wobble frequency
Function parameters
Default
Modify
value
○
0.00Hz
○
0.00Hz
○
0.00Hz
○
0.00Hz
○
0.0%
○
0.0%
○
5.0s
○
5.0s
Need help?
Do you have a question about the Goodrive200A Series and is the answer not in the manual?
Questions and answers
Ou2 fault
An Ou2 fault on the INVT Goodrive200A Series indicates an IGBT Ph-V fault. Possible causes include:
- IGBT module fault
- Misoperation caused by interference
- Poor connection of driving wires
- Improper grounding
To fix it:
- Increase the acceleration time
- Change the power unit
- Check the driving wires
- Inspect external equipment and eliminate interference
- Ensure proper grounding
This answer is automatically generated