GD200A series VFD
Function
Name
code
Lower limit of
P06.17
AO1 output
Corresponding
P06.18
AO1 output to
the lower limit
Upper limit of
P06.19
AO1 output
Corresponding
P06.20
AO1 output to
the upper limit
AO1 output
P06.21
filter time
Lower limit of
P06.22
AO2 output
Corresponding
AO2 output to
P06.23
the lower limit
Upper limit of
P06.24
AO2 output
Corresponding
AO2 output to
P06.25
the upper limit
AO2 output
P06.26
filter time
Lower limit of
P06.27
HDO output
Corresponding
HDO output to
P06.28
the lower limit
Upper limit of
P06.29
HDO output
Corresponding
HDO output to
P06.30
the upper limit
Description
13: High speed pulse HDI input value
14: MODBUS communication set value 1
15: MODBUS communication set value 2
22: Torque current (relative to triple the motor
rated current)
23: Ramp reference frequency(with sign)
The above function codes define the relative
relationship between the output value and analog
output. When the output value exceeds the range
of set maximum or minimum output, it will count
according to the low-limit or upper-limit output.
When the analog output is current output, 1mA
equals to 0.5V.
In different cases, the corresponding analog
output of 100% of the output value is different. For
details, see section 7.10 PID control.
A
O
10V(20mA)
0.0%
Setting range of P06.17: -100.0%–P06.19
Setting range of P06.18: 0.00V–10.00V
Setting range of P06.19: P06.17–100.0%
Setting range of P06.20: 0.00V–10.00V
Setting range of P06.21: 0.000s–10.000s
Setting range of P06.22:
Setting range of P06.23: 0.00V–10.00V
Setting range of P06.24: P06.22–100.0%
Setting range of P06.25: 0.00V–10.00V
Setting range of P06.26: 0.000s–10.000s
Setting range of P06.27: 0.000s–10.000s
Setting range of P06.28: 0.00–50.00kHz
Setting range of P06.29: P06.27–100.0%
Setting range of P06.30: 0.00–50.00kHz
Setting range of P06.31: 0.000s–10.000s
-66-
100.0%
0.0%–P06.24
Function parameters
Default
Modify
value
0.0%
0.00V
100.0%
10.00V
0.000s
0.0%
0.00V
100.0%
10.00V
0.000s
0.00%
0.00kHz
100.0%
50.00
kHz

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive200A Series and is the answer not in the manual?

Questions and answers

Anand
April 1, 2025

Ou2 fault

User image 67eb64e07723d
1 comments:
Mr. Anderson
April 1, 2025

An Ou2 fault on the INVT Goodrive200A Series indicates an IGBT Ph-V fault. Possible causes include:

- IGBT module fault
- Misoperation caused by interference
- Poor connection of driving wires
- Improper grounding

To fix it:

- Increase the acceleration time
- Change the power unit
- Check the driving wires
- Inspect external equipment and eliminate interference
- Ensure proper grounding

This answer is automatically generated