Note: The code is consisted of 16 bits including high 8 bits and low 8 bits. High 8 bits mean the
motor type series and low 8 bits mean the derived motor types of the series. For example, 0110H
means Goodrive200A vector VFDs.

9.5.3 Fieldbus ratio values

The communication data is expressed by hex in actual application and there is no radix point in hex.
For example, 50.12Hz cannot be expressed by hex so 50.12 can be magnified by 100 times into
5012, so hex 1394H can be used to express 50.12.
A non-integer can be timed by a multiple to get an integer and the integer can be called fieldbus ratio
values.
The fieldbus ratio values are referred to the radix point of the setting range or default value in the
function parameter list. If there are figures behind the radix point (n=1), then the fieldbus ratio value
n
10
m is
. Take the table as the example:
Function
code
Wake-up from sleep
P01.20
delay time
P01.21
Restart after power off
If there is one figure behind the radix point in the setting range or the default value, then the fieldbus
ratio value is 10. If the data received by the upper monitor is 50, then the "hibernation restore delay
time" is 5.0 (5.0=50÷10).
If MODBUS communication is used to control the hibernation restore delay time as 5.0s. Firstly, 5.0
can be magnified by 10 times to integer 50 (32H) and then this data can be sent.
After the VFD receives the command, it will change 50 into 5 according to the fieldbus ratio value
and then set the hibernation restore delay time as 5s.
Another example, after the upper monitor sends the command of reading the parameter of
Code low 8 bit
0x08
0x09
0x0a
GD
0x0b
0x0c
0x0d
Name
0.0–3600.0s (valid when P01.19=2)
0: Disable
1: Enable
VFD
Write
address
command
GD100 simple vector VFDs
Details
Data
Parameters
address
number
-142-
Communication protocol
Meaning
GD35 vector VFDs
GD35-H1 vector VFDs
GD300 vector VFDs
GD200A general VFDs
GD10 mini VFDs
Default
value
0.0s
0
CRC
check
Modify

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive200A Series and is the answer not in the manual?

Questions and answers

Anand
April 1, 2025

Ou2 fault

User image 67eb64e07723d
1 comments:
Mr. Anderson
April 1, 2025

An Ou2 fault on the INVT Goodrive200A Series indicates an IGBT Ph-V fault. Possible causes include:

- IGBT module fault
- Misoperation caused by interference
- Poor connection of driving wires
- Improper grounding

To fix it:

- Increase the acceleration time
- Change the power unit
- Check the driving wires
- Inspect external equipment and eliminate interference
- Ensure proper grounding

This answer is automatically generated