motor insulator, compensation must be made by adding an output reactor. When a VFD is used to
drive multiple motors, take the total length of the motor cables (that is, sum of the lengths of the
motor cables) into account. When the total length is longer than 50 m, an output reactor must be
added on the output side of the VFD. If the distance between the VFD and motor ranges from 50 m
to 100 m, select the reactor according to the following table. If the distance is longer than 100 m,
contact INVT's technical support. The mapping between VFD models and reactors is as follows:
VFD model
GD200A-0R7G-4
GD200A-1R5G-4
GD200A-2R2G-4
GD200A-004G/5R5P-4
GD200A-5R5G/7R5P-4
GD200A-7R5G/011P-4
GD200A-011G/015P-4
GD200A-015G/018P-4
GD200A-018G/022P-4
GD200A-022G/030P-4
GD200A-030G/037P-4
GD200A-037G/045P-4
GD200A-045G/055P-4
GD200A-055G/075P-4
GD200A-075G/090P-4
GD200A-090G/110P-4
GD200A-110G/132P-4
GD200A-132G/160P-4
GD200A-160G/185P-4
GD200A-185G/200P-4
GD200A-200G/220P-4
GD200A-220G/250P-4
GD200A-250G/280P-4
GD200A-280G/315P-4
GD200A-315G/355P-4
GD200A-355G/400P-4
GD200A-400G-4
GD200A-450G-4
GD200A-500G-4
Note:
1. The rated derate voltage of the input reactor is 2%± 15%.
2. The power factor of the input side is above 90% after adding DC reactor.
Input reactor
ACL2-1R5-4
ACL2-1R5-4
ACL2-2R2-4
ACL2-004-4
ACL2-5R5-4
ACL2-7R5-4
ACL2-011-4
ACL2-015-4
ACL2-018-4
ACL2-022-4
ACL2-037-4
ACL2-037-4
ACL2-045-4
ACL2-055-4
ACL2-075-4
ACL2-110-4
ACL2-110-4
ACL2-160-4
ACL2-160-4
ACL2-200-4
ACL2-200-4
ACL2-280-4
ACL2-280-4
ACL2-280-4
ACL2-350-4
Standard
Standard
Standard
Standard
-167-
Peripheral options and parts
DC reactor
Output reactor
/
/
/
/
/
/
/
/
/
/
/
DCL2-037-4
DCL2-045-4
DCL2-055-4
DCL2-075-4
DCL2-090-4
DCL2-132-4
DCL2-132-4
DCL2-160-4
DCL2-220-4
DCL2-220-4
DCL2-280-4
DCL2-280-4
DCL2-280-4
DCL2-315-4
DCL2-400-4
DCL2-400-4
DCL2-500-4
DCL2-500-4
OCL2-1R5-4
OCL2-1R5-4
OCL2-2R2-4
OCL2-004-4
OCL2-5R5-4
OCL2-7R5-4
OCL2-011-4
OCL2-015-4
OCL2-018-4
OCL2-022-4
OCL2-037-4
OCL2-037-4
OCL2-045-4
OCL2-055-4
OCL2-075-4
OCL2-110-4
OCL2-110-4
OCL2-160-4
OCL2-200-4
OCL2-200-4
OCL2-200-4
OCL2-280-4
OCL2-280-4
OCL2-280-4
OCL2-350-4
OCL2-350-4
OCL2-400-4
OCL2-500-4
OCL2-500-4

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive200A Series and is the answer not in the manual?

Questions and answers

Anand
April 1, 2025

Ou2 fault

User image 67eb64e07723d
1 comments:
Mr. Anderson
April 1, 2025

An Ou2 fault on the INVT Goodrive200A Series indicates an IGBT Ph-V fault. Possible causes include:

- IGBT module fault
- Misoperation caused by interference
- Poor connection of driving wires
- Improper grounding

To fix it:

- Increase the acceleration time
- Change the power unit
- Check the driving wires
- Inspect external equipment and eliminate interference
- Ensure proper grounding