    Installer manual Siata V132 - SFE - Table of contents Table of contents Generalities ......... . 5 1.1.
  • Page 3 Installer manual Siata V132 - SFE - Table of contents System sizing ........23 4.1.
  • Page 4 Installer manual Siata V132 - SFE - Table of contents Commissioning ........52 7.1.
  • Page 5: Generalities

    18.11.2016 First edition 19.04.2017 New chapter: Valve connection to piping 1.3. Manufacturer identifier, product Manufacturer: Pentair Manufacturing Italy Srl Via Masaccio, 13 56010 Lugnano di Vicopisano (PI) – Italy Product: Siata V132 - SFE 1.4. Intended use The device is intended for residential, commercial or light industry environment (ref. EN 50081-1) use only and it is purpose-built for treatment and softening of water coming from supply network.
  • Page 6: Abbreviations Used

    Installer manual Siata V132 - SFE - Generalities 1.5. Abbreviations used DF............Down Flow Inj ............Injector DLFC ............Drain Line Flow Controller BLFC / Refill Flow Controller....Brine Line Flow Controller QC............Quick Connect Regen ............Regeneration S&S ............Seal & Spacer SBV............
  • Page 7: Procedure For Technical Support

    Pentair Quality System EMEA products benefit, under specific conditions, from a manufacturer warranty that may be invoked by Pentair’s direct customers. Users should contact the vendor of this product for applicable conditions and in case of a potential warranty claim.
  • Page 8: Safety

    Installer manual Siata V132 - SFE - Safety Safety 2.1. Safety pictograms definition Caution Warning Warns of a risk of minor injury or major Warns against serious personal injury material damage to the device or and damage to health. environment. Danger...
  • Page 9: Hazards

    Installer manual Siata V132 - SFE - Safety 2.3. Hazards All the safety and protection instructions contained in this document must be observed in order to avoid temporary or permanent injury, damage to property or environmental pollution. At the same time, any other legal regulations, accident prevention and environmental protection measures, as well as any recognized technical regulations relating to appropriate and risk-free methods of working which apply in the country and place of use of the device must be adhered to.
  • Page 10: Hygiene And Sanitization

    Installer manual Siata V132 - SFE - Safety 2.4. Hygiene and sanitization 2.4.1. Sanitary issues Preliminary checks and storage • Check the integrity of the packaging. Check that there is no damage and no signs of contact with liquid to make sure that no external contamination occurred. •...
  • Page 11: Description

    Installer manual Siata V132 - SFE - Description Description 3.1. Valve versions 3.1.1. Twin pilots The pressure distributor pilot is mounted directly on top of the V132, in this case inlet water is the control fluid and feeds the pilot circuit from the top collector. A controller with a proper camshaft (called twin pilot camshaft) must be mounted on top of the valve and linked to the pilot stems.
  • Page 12: Technical Specifications

    Installer manual Siata V132 - SFE - Description 3.2. Technical specifications Design specifications/ratings Valve body ..........Glassfiber reinforced ABS Rubber components ....... NBR Valve material certification ....DM174, ACS, KTW, W270 Weight (valve with controller) ....2.5 kg (max.) Recommended operating pressure ..1.5 - 6 bar (22 - 87 psi) Hydrostatic test pressure.......
  • Page 13: Performance Flow Rate Characteristics

    Installer manual Siata V132 - SFE - Description 3.2.1. Performance flow rate characteristics The graph shows the pressure drop created by the valve itself at different flow rates. It makes it possible to predetermine the maximum flow rate going through the valve depending on the system settings (inlet pressure etc).
  • Page 14: Outline Drawing

    Installer manual Siata V132 - SFE - Description 3.3. Outline drawing 14 / 88 Ref. MKT-IM-003 / B - 19.04.2017...
  • Page 15 Installer manual Siata V132 - SFE - Description PAGE INTENTIONALLY LEFT BLANK Ref. MKT-IM-003 / B - 19.04.2017 15 / 88...
  • Page 16: Description And Components Location

    Installer manual Siata V132 - SFE - Description 3.4. Description and components location 3.4.1. Valve with twin pilots Long manifold SFE Controller Injector Extra pressure output connection LCD Display Brine line connection Down button Inlet Regen button Mixing device Up button Outlet + turbine Volumetric sensor input Drain line connection...
  • Page 17: Valve With External Pilots

    Installer manual Siata V132 - SFE - Description 3.4.2. Valve with external pilots Note Only the components that differ from the twin pilots valve are described below. Refer to chapter 3.4.1. Valve with twin pilots, page 16 for more information. Camshaft External pilots Short manifold...
  • Page 18: System Regeneration Cycle (4-Cycle Operation)

    Installer manual Siata V132 - SFE - Description 3.5. System regeneration cycle (4-cycle operation) Service — cycle C0 Untreated water is directed down through the resin bed and up through the riser tube. The hardness ions attach themselves to the resin and are removed from the raw water being exchanged on the resin beads towards sodium ions.
  • Page 19 Installer manual Siata V132 - SFE - Description Note For illustration purpose only. Always verify inlet and outlet marking on the valve. Valve Valve SERVICE BACKWASH From brine tank Valve Valve BRINE DRAW / FAST RINSE SLOW RINSE C2 and C3 Ref.
  • Page 20 Installer manual Siata V132 - SFE - Description Backwash flow diagram Service flow diagram Inlet Outlet Inlet Outlet Drain Drain Brine draw diagram Slow rinse diagram Inlet Outlet Inlet Outlet Drain Drain Fast rinse diagram Inlet Outlet Drain 20 / 88 Ref.
  • Page 21: Options Available On The Valve

    Installer manual Siata V132 - SFE - Description 3.6. Options available on the valve Backwash flow regulators Backwash flow regulator (1) is positioned in the lower part of the valve. It is accessed by unscrewing protective cap (2). Valves equipped with this accessory are fitted with a flow control set offering the following maximum outputs: Max output Code...
  • Page 22 Installer manual Siata V132 - SFE - Description Note There is no automatic bypass during a fast rinse cycle. But once the mixing device has been set, it connects the inlet and outlet of the valve. So during the fast rinse phase with a mixing device, it is possible that a flow of untreated water flows into the outlet.
  • Page 23: System Sizing

    Installer manual Siata V132 - SFE - System sizing System sizing 4.1. Recommendations 4.1.1. Injector/DLFC/BLFC-Valve configuration Tank diameter Resin volume DLFC Injector DF [in] [l/h] [gpm] Washers Brown Blue Blue Black 1450 Black 1450 4.2. Sizing a softener (single unit) 4.2.1.
  • Page 24 Installer manual Siata V132 - SFE - System sizing Depending on the inlet water hardness, the service velocity for standard softening has to be between: Inlet water hardness Service velocity °F °dH [mg/l as CaCO [bed volume per hour] °TH 8 - 40 <...
  • Page 25: Determining The Required Volume Of Resin

    Installer manual Siata V132 - SFE - System sizing 4.2.2. Determining the required volume of resin When sizing a softener, make sure that the volume of resin in the tank (bed volume) will be sufficient so that even when the peak flow rate is reached, the velocity is still between the above values depending on the hardness.
  • Page 26 Installer manual Siata V132 - SFE - System sizing Resin exchange capacity as a function of the salt dosage for standard efficiency: Salt amount Corresponding resin exchange °F.m °d.m [g/L capacity in [g/L ] as CaCO resin resin 29.9 2.99 1.67 37.5 3.75...
  • Page 27 Installer manual Siata V132 - SFE - System sizing To calculate the system mass capacity: with: capacity resin resin ex : system mass capacity [g as CaCO 3 ]] capacity : volume of resin [L] resin : resin exchange capacity [g/L as CaCO resin ex resin...
  • Page 28: Valve Configuration

    Installer manual Siata V132 - SFE - System sizing 4.2.4. Valve configuration Knowing the volume of resin, tank size and specifications of the resin, it is possible to determine the required valve configuration. The resin specification will give the backwash velocity, as well as the brine draw and slow rinse velocity that must be respected in order to ensure a proper regeneration of the unit.
  • Page 29: Cycle Time Calculation

    Installer manual Siata V132 - SFE - System sizing 4.2.5. Cycle time calculation From this point, the volume of resin, the tank size and the capacity of the softener is determined. Next step is to calculate the regeneration cycle time, which depends on the valve configuration and once again on the resin specifications.
  • Page 30: Brine Refill - Cycle

    Installer manual Siata V132 - SFE - System sizing To calculate slow rinse duration: The volume of water to be used for slow rinse is given in the resin manufacturers specifications. Generally speaking, it is advised that between 2 and 4 BV of water is used to perform the slow rinse after brine draw.
  • Page 31: Injection Flow Rates (Tables)

    Installer manual Siata V132 - SFE - System sizing 4.3. Injection flow rates (tables) The following tables represent the injector flow rate as a function of the inlet pressure for the different injector sizes Blue ejector performance Brown ejector performance Pressure [bar] Pressure [bar] Red ejector performance...
  • Page 32: Installation

    Installer manual Siata V132 - SFE - Installation Installation Caution It is strictly forbidden for non-qualified persons to access the system's internal components in order to perform any kind of technical operation. 5.1. Warnings The manufacturer will not be held liable for any damage or injury to persons or property resulting from improper use of the device, or use not in line with the following instructions.
  • Page 33 Installer manual Siata V132 - SFE - Installation Length of connection pipes between valve and lower distribution system The connection pipe must be cut between 12 to 17 mm, measured from the upper edge of the tank. Remove the sharp edges (1 mm x 45°) to avoid damage to the seal during installation. See drawing below.
  • Page 34: General

    Installer manual Siata V132 - SFE - Installation 5.3.2. General • Use only brine salts designed for water softening. Do not use ice melt salt, block, or rock salts; • Keep the media tank in the upright position. Do not turn on its side, upside down, or drop. Turning the tank upside down may cause media to enter the valve or might plug the upper screen;...
  • Page 35: Mechanical

    Installer manual Siata V132 - SFE - Installation 5.3.5. Mechanical • Do not use PTFE (plumber’s tape) lubricants such as vaseline, oils, or hydrocarbon-based lubricants. Use only 100% silicone lubricants; • All plastic connections should be hand tightened. PTFE (plumber’s tape) may be used on connections that do not use an O-ring seal.
  • Page 36: Block Diagram And Configuration Example

    Installer manual Siata V132 - SFE - Installation 5.4. Block diagram and configuration example Configuration example Block diagram By-pass Main inlet Gauge Gauge User’s line Check valve to prevent water harm and eventual hot water returns. Turbine Mixer Drain Valve Brine line Suggested options Resin tank...
  • Page 37: Diagrams Of Softening Systems And Connections

    Installer manual Siata V132 - SFE - Installation 5.5. Diagrams of softening systems and connections Connections drawings for Siata V132-SFE with 3 pilots. Connections drawings for Siata V132-SFE with 4 pilots. Ref. MKT-IM-003 / B - 19.04.2017 37 / 88...
  • Page 38: Valve Connection To Piping

    Installer manual Siata V132 - SFE - Installation 5.6. Valve connection to piping The connections should be hand tightened using PTFE (plumber’s tape) on the threads if using the threaded connection type. In case of heat welding (metal type connection), the connections should not be made to the valve when soldering.
  • Page 39 • In any case, any failure caused by improper installations and/or piping connections may void the warranty of Pentair products. • In the same way, using lubricant* on the valve thread is not allowed and will void the warranty for the valve and tank.
  • Page 40: Connections (Electrical)

    Installer manual Siata V132 - SFE - Installation 5.7. Connections (electrical) Output dry contact type Input dry contact type Chlorine cell or End cycle signal Reed sensor meter or Siata meter (Siata meter has 3 cables) AC adapter input (low voltage) 40 / 88 Ref.
  • Page 41: Bypassing

    Installer manual Siata V132 - SFE - Installation 5.8. Bypassing A bypass valve system has to be installed on all water conditioning systems. Bypass valves isolate the conditioner from the water system and allow unconditioned water to be used. Service or routine maintenance procedures may also require the system to be bypassed.
  • Page 42: Automatic Bypass

    Installer manual Siata V132 - SFE - Installation 5.8.2. Automatic Bypass The automatic proportional bypass accessory enhances the system with following functions when fitted upstream of the water treatment system: • Supply of untreated water during regeneration cycle 4C. In this cycle the valve does not provide hard water bypass during the regeneration.
  • Page 43: Drain Line Connection

    Installer manual Siata V132 - SFE - Installation 5.9. Drain line connection Note Standard commercial practices are expressed here. Local codes may require changes to the following suggestions. Check with local authorities before installing a system. The unit should be above and not more than 6.1 m (20 ft) from the drain. Use a 22 mm hose tube. The drain line may be elevated up to 1.8 m (6 ft) providing the run does not exceed 4.6 m (15 ft) and water pressure at the conditioner is not less than 2.76 bar (40 psi).
  • Page 44: Overflow Line Connection

    Installer manual Siata V132 - SFE - Installation 5.10. Overflow line connection In the event of a malfunction, the brine tank overflow fitting will direct “overflow” to the drain instead of spilling on the floor. This fitting should be on the side of the cabinet or brine tank. Most tank manufacturers include a post for the tank overflow connector.
  • Page 45: Programming

    Installer manual Siata V132 - SFE - Programming Programming 6.1. General information • In battery-operated mode, regeneration is not carried out and the parameters cannot be edited; • The SFE controller allows you to manage your installation via clock control or volumetric control. The controller will automatically initiate regenerations cycles based upon the programmed regeneration mode and the programmed parameters;...
  • Page 46: Advanced Programming

    Installer manual Siata V132 - SFE - Programming Day of week Set the current day of the week. to edit this parameter. Press to validate and switch to the next parameters. Days enabled for regeneration Set the days enabled for regeneration. The display shows "dx y" where "x"...
  • Page 47 Installer manual Siata V132 - SFE - Programming to edit this parameter. Press to validate and switch to the next parameters. Interval time between regenerations Set the interval time (hours) between regenerations. Note This parameter is displayed after the regeneration start mode only if an interval start has been selected (SH:03).
  • Page 48 Installer manual Siata V132 - SFE - Programming where : • d.xxx : incoming water hardness, in French degrees [°f] or [ppm]; • do.xx: desired outgoing water hardness, in French degrees [°f]; • C:xx: exchange capacity of the regenerating resin used, expressed in [°f x m /L] or in [g/L ] of resin...
  • Page 49 Installer manual Siata V132 - SFE - Programming Number of regenerations before a salt alarm is generated Set the number of regenerations before a salt alarm is generated. to edit this parameter. Press to validate and switch to the next parameters. The following formula is used to calculate the number of regenerations before a salt alarm is generated : SA = [(M.xxx) x 1000] / [(L.xxx) x (G.xx)]...
  • Page 50: Statistics

    Installer manual Siata V132 - SFE - Programming Chlorine driver activated Set the chlorine driver on or off. to edit this parameter. Press to validate and switch to the next parameters. Note This functionality only works if the controller has chlorine driver. Volume restored / not restored Set to determine whether the volume is restored (UlMM) or not restored (UdlF).
  • Page 51: Resetting The Eeprom

    Installer manual Siata V132 - SFE - Programming 6.3.2. Resetting the EEPROM To reset the EEPROM to the default values, the controller must be in the service condition (no regeneration cycle running and clock displayed). Open the Statistics menu. → See 6.3.1. Statistics, page 50. Press and release Press and release Press and release...
  • Page 52: Commissioning

    Installer manual Siata V132 - SFE - Commissioning Commissioning 7.1. Start up procedure 1. With the bypass still in bypass position (inlet and outlet manual valve closed), plug in the SFE controller to the power source. 2. If not done yet proceed to programming according to the system specification. See “Programming”, page 45.
  • Page 53: Sanitization

    Installer manual Siata V132 - SFE - Commissioning 11. Fill the brine tank with salt. It is possible to mark the level of water in the brine tank when it is completely refilled with water and full of salt. In the future, after each regeneration, you can visually control that the quantity of water refilled should be between the 2 marks done.
  • Page 54: Electro Chlorination

    Installer manual Siata V132 - SFE - Commissioning Brine tank softeners Backwash the conditioner and add the required amount of hypochlorite solution to the well of the brine tank. The brine tank should have water in it to permit the solution to be carried into the conditioner.
  • Page 55 Installer manual Siata V132 - SFE - Commissioning PAGE INTENTIONALLY LEFT BLANK Ref. MKT-IM-003 / B - 19.04.2017 55 / 88...
  • Page 56: Operation

    Installer manual Siata V132 - SFE - Operation Operation 8.1. Recommendations • Use only regeneration salts designed for water softening EN973. • For optimal system operation, the use of clean salt free from impurities is recommended (for example salt pellets). •...
  • Page 57: Maintenance

    Installer manual Siata V132 - SFE - Maintenance Maintenance Mandatory Cleaning and maintenance shall take place at regular intervals in order to guarantee the proper functioning of the complete system. Danger Any valve maintenance operation must be carried out in the absence of hydraulic pressure. For this reason, disconnect the water delivery line to the valve.
  • Page 58: Cleaning And Maintenance

    Installer manual Siata V132 - SFE - Maintenance 9.2. Cleaning and maintenance 9.2.1. Cleaning and maintenance Before any cleaning or maintenance procedure, complete the following step : Operation Caution These operations need to be performed before any cleaning or maintenance procedure. Unplug the wall-mounted transformer.
  • Page 59 Installer manual Siata V132 - SFE - Maintenance Ref. MKT-IM-003 / B - 19.04.2017 59 / 88...
  • Page 60: Motor Replacement

    Installer manual Siata V132 - SFE - Maintenance 9.2.3. Motor replacement Operation Using a screwdriver, unscrew the screw (9). Remove the controller (6) from the valve (8). Using a screwdriver, unscrew the four screws (1). Remove the front panel (2) from the controller (6). Using a screwdriver, unscrew the two screws (10).
  • Page 61 Installer manual Siata V132 - SFE - Maintenance Ref. MKT-IM-003 / B - 19.04.2017 61 / 88...
  • Page 62: Cleaning The Injector And The Injector Screen

    Installer manual Siata V132 - SFE - Maintenance 9.2.5. Cleaning the injector and the injector screen Operation Using a screwdriver, unscrew the screw (2). Remove the controller (1) from the valve (9). Manually actuate the pistons (8) to drain the water from inside the valve. Using a screwdriver, unscrew the three screws (3).
  • Page 63 Installer manual Siata V132 - SFE - Maintenance Ref. MKT-IM-003 / B - 19.04.2017 63 / 88...
  • Page 64: Replacing The Drain Connection

    Installer manual Siata V132 - SFE - Maintenance 9.2.6. Replacing the drain connection Operation Unplug the pilots to drain tube (3). Push out the two locking pins (1). Slip off and change the drain manifold (2). Replace and grease all the O-rings with silicone grease (cod. 8500). Reverse above procedure steps to rebuild.
  • Page 65 Installer manual Siata V132 - SFE - Maintenance Ref. MKT-IM-003 / B - 19.04.2017 65 / 88...
  • Page 66: Replacing The Twin Pilots

    Installer manual Siata V132 - SFE - Maintenance 9.2.7. Replacing the twin pilots Operation Using a screwdriver, unscrew the screw (1). Remove the controller (2) from the valve (9). Manually actuate the pistons (3) to drain out the water inside the valve to the drain. Using a screwdriver, unscrew the three screws (7).
  • Page 67 Installer manual Siata V132 - SFE - Maintenance Ref. MKT-IM-003 / B - 19.04.2017 67 / 88...
  • Page 68: Replacing The Pilots (External Drivers Connections)

    Installer manual Siata V132 - SFE - Maintenance 9.2.8. Replacing the pilots (external drivers connections) Operation Using a screwdriver, unscrew the screw (1). Remove the controller with the pilots (4) from the valve body (3). Unscrew and remove the screws, the nuts and the washers (2). Remove the clamping plate (6).
  • Page 69 Installer manual Siata V132 - SFE - Maintenance Ref. MKT-IM-003 / B - 19.04.2017 69 / 88...
  • Page 70: Replacing The Internal Pistons And The Seals And Spacers

    Installer manual Siata V132 - SFE - Maintenance 9.2.9. Replacing the internal pistons and the seals and spacers 9.2.9.1 Disassembly Note The procedure to disassemble the inlet and outlet pistons is the same. Operation Note Use special tools from the 2238/05 kit to disassemble the valve internal parts. Caution...
  • Page 71 Installer manual Siata V132 - SFE - Maintenance Ref. MKT-IM-003 / B - 19.04.2017 71 / 88...
  • Page 72 Installer manual Siata V132 - SFE - Maintenance 9.2.9.2 Assembly Note The procedure to assemble the inlet and outlet pistons is the same. Operation Note Use special tools from the 2238/05 kit to assemble the valve internal parts. Note Before reassembling, grease with silicone grease (cod. 8500) : - The inlet and outlet pistons;...
  • Page 73 Installer manual Siata V132 - SFE - Maintenance Ref. MKT-IM-003 / B - 19.04.2017 73 / 88...
  • Page 74: Troubleshooting

    Installer manual Siata V132 - SFE - Troubleshooting Troubleshooting Issue Cause Reset and recovery Twin pilot valve : Before closing the inlet water supply, disconnect the drain rubber tube and check if there is a leakage from that tube. In case there is one, close inlet water pressure and change the twin pilot assembly.
  • Page 75 Installer manual Siata V132 - SFE - Troubleshooting Issue Cause Reset and recovery If the water leaking from the drain is softened check for damages on the outlet part of the valve, in particular outlet piston or seals and spacers. Otherwise check for damages on the Leaks to the drain inlet part of the valve.
  • Page 76 Installer manual Siata V132 - SFE - Troubleshooting Issue Cause Reset and recovery Close the outlet of the valve, check that the pressure gauge shows a pressure of at least 2 bars. If it is lower, the pressure is insufficient. If the pressure Low water pressure at the inlet.
  • Page 77: Spare Parts

    Installer manual Siata V132 - SFE - Spare parts Spare parts 11.1. Fittings For V132 with quick inlet and outlet ports Packaging Item Part number Description quantity 2265-A/05 Kit Fitting ¾" BSP female Threaded (NYLON) 2265-B/05 Kit Fitting 1" BSP female Threaded (NYLON) 2265-C/05 Kit Fitting 1 ¼"...
  • Page 78: Valve Parts List

    Installer manual Siata V132 - SFE - Spare parts 11.2. Valve parts list 78 / 88 Ref. MKT-IM-003 / B - 19.04.2017...
  • Page 79 Installer manual Siata V132 - SFE - Spare parts Packaging Item Part number Description quantity 1+17+27 2256-K01/05 Valve Body service kit 2256-K02/05 Valve Body service kit volumetric 2222/05 Internal Turbine assembly 2231-B/05 Injector Assy - Blue 2231-F/05 Injector for filter valves 2231-G/05 Injector Assy - Grey 2231-M/05...
  • Page 80 Installer manual Siata V132 - SFE - Spare parts Packaging Item Part number Description quantity K-2224-A/05 Turbine sensor holder nut K-70-1 Flow control Ø3-mm. & 320 L/h (#70-1) K-70-2 Flow control Ø3.5-mm. & 480 L/h (#70-2) K-70-3 Flow control Ø4-mm. & 700 L/h (#70-3) K-70-4 Flow control Ø5-mm.
  • Page 81 Installer manual Siata V132 - SFE - Spare parts Packaging Item Part number Description quantity 1002-D32 Bottom Strainer (Ø 32.mm) 1001-32I Upper Strainer Backwash flow control kit without backwash flow K-10026 control washer kit K-10028 Driver Replica Connection K-9-S/05 Drain connection lock pin K-9/05 Inlet/Outlet connection lock pin K-46-1/05...
  • Page 82: Sfe Spare Parts

    Installer manual Siata V132 - SFE - Spare parts 11.3. SFE spare parts 82 / 88 Ref. MKT-IM-003 / B - 19.04.2017...
  • Page 83 Installer manual Siata V132 - SFE - Spare parts Packaging Item Part number Description quantity 856-SFE-K1 SFE controller front plate kit with standard label K-7930-24 Electronic board SFE standard w/ chloride driver K-7930-23 Electronic board SFE standard 94-R7K/05 Standard 12V motor kit K-10117 SFE back connector kit w/ internal wiring K-10110...
  • Page 84 Installer manual Siata V132 - SFE - Spare parts Packaging Item Part number Description quantity 2221-2/05 Kit Cam 201 - 2 pilots standard 2221-2FBW/05 Kit Cam 210 - 2 pilots for profiler 2221-3CU/05 Kit Cam 301 - 3 pilots outlet shut-off 2221-3CA/05 Kit Cam 303 - 3 pilots suction shut-off no refill 2221-4AU/05...
  • Page 85: Accessories

    Installer manual Siata V132 - SFE - Spare parts 11.4. Accessories Brine valve Packaging Item Code Description quantity BR1-100/05 Brine Valve BR With Flexible Pole Bypass valve Packaging Item Code Description quantity BP-D/06 Direct Bypass With Prop. Mixing + Check Valve BP-D1/06 Direct Bypass No Mixing + Check Valve BP-DN1/06...
  • Page 86 Installer manual Siata V132 - SFE - Spare parts Meters Packaging Item Code Description quantity 2296/05 Turbine Meter G 1 ½" 2297-2M/05 Turbine Meter G ¾" (2 Magnet) 2297/05 Turbine Meter G ¾" Maintenance parts Packaging Item Code Description quantity 2238/05 Kit Maintenance Tools 8500...
  • Page 87: Scrapping

    This will help to reduce the impact on the environment, health, safety and help to promote recycling. Pentair do not collect used product for recycling. Contact your local recycling centre for more information.