Active Airflow Circulation; Setpoint Range; Cooling/Heating Masterhood; Airflow Direction Range - Daikin Madoka BRC1H519W7 Installer And User Reference Manual

Wired remote controller
Hide thumbs Also See for Madoka BRC1H519W7:
Table of Contents

Advertisement

15.5.20 Active airflow circulation

15.5.21 Setpoint range

15.5.22 Cooling/Heating masterhood

15.5.23 Airflow direction range

BRC1H519W+K+S7
Madoka wired remote controller
4P513689-1E – 2020.12
INFORMATION
The availability of this function depends on the type of indoor unit.
Enable Active airflow circulation to have a more even temperature distribution in
the room.
When Active airflow circulation is enabled, indoor unit fan speed and airflow
direction get controlled automatically, making manual fan speed and airflow
direction changes impossible.
Set a limitation to the temperature setpoint range of both Cooling and Heating
operation.
INFORMATION
This function cannot be used when the indoor units are controlled by a centralised
controller.
INFORMATION
The default setpoint range limits for both Heating and Cooling operation is
[16°C-32°C], regardless of whether or not "Setpoint range limitation" is enabled. It is
not possible to exceed these limits.
Set an indoor unit (or group of indoor units) as Cooling/Heating master. When
multiple indoor units are connected to an outdoor unit, one of these units (or a
group of indoor units, in case of group control) needs to be set as Cooling/Heating
master. The other units/groups then become Cooling/Heating slaves, and are
restricted in their operation by the master (e.g. one outdoor unit does not allow for
one indoor unit to run in Cooling operation while another runs in Heating
operation).
When an indoor unit or group of indoor units is set as Cooling/Heating master, the
other units/groups automatically become its slaves. To turn a slave unit into the
master, first connect the app to the controller controlling the currently active
master and release it from its masterhood, then set the (slave) unit as master.
Set the indoor unit airflow direction range according to the installation location.
This function is available for floorstanding indoor units only. The maximum number
of indoor units for which you can make these settings is 16.
Left
15
Centre
About the app
|
Right
Installer and user reference guide
111