Daikin Madoka BRC1H519W7 Installer And User Reference Manual page 20

Wired remote controller
Hide thumbs Also See for Madoka BRC1H519W7:
Table of Contents

Advertisement

5
|
Operation
Auto
Installer and user reference guide
20
INFORMATION
In case of indoor unit setpoint logic, the system cannot run in Auto operation mode.
Therefore, to allow for Auto operation mode, go for remote controller setpoint logic.
For more information, see the Madoka Assistant app and
The Auto operation mode logic depends on the set setpoint logic (Madoka
Assistant app setting).
Single setpoint
C2
+ C1
SP
+ C1
C2
DIFF Minimum setpoint differential between the Heating and
+C1 Changeover setpoint (with guard timer)
C2 Forced changeover setpoint
0.5°C~2°C Field settable temperature intervals between setpoints
INFORMATION
The default value of the settable temperature range (0.5°C~2°C) is 0.5°C.
A changeover from the one operation mode to the other occurs in the following
cases:
Case 1: primary changeover ( +C1)
A changeover occurs from the moment the room temperature rises above/drops
below the Cooling/Heating changeover setpoint (C1), and the guard timer has run
out.
Example:
0.5°C
2°C
~
0.5°C
~
2°C
0.5°C
2°C
~
0.5°C
~
2°C
Cooling setpoint
Heating setpoint
the Cooling setpoint
4
"Setpoint
logic" [
 108].
Dual setpoint
C2
0.5°C
2°C
~
+ C1
0.5°C
~
2°C
SP
DIFF
SP
0.5°C
2°C
~
+ C1
0.5°C
~
2°C
C2
BRC1H519W+K+S7
Madoka wired remote controller
4P513689-1E – 2020.12