15.5.18 Setback

BRC1H519W+K+S7
Madoka wired remote controller
4P513689-1E – 2020.12
18º 19º 20º 21º 22º 23º 24º 25º 26º 27º 28º 29º
18º 19º 20º 21º 22º 23º 24º 25º 26º 27º 28º 29º
DIFF Minimum setpoint differential
INFORMATION
When the system is controlled by central control equipment, control of the system
by the controller is limited. When this is the case, it is not possible to set dual
setpoint logic in the Madoka Assistant app.
INFORMATION
When the indoor units are under control of a centralised controller, only indoor unit
setpoint logic is possible.
INFORMATION
In case of indoor unit setpoint logic, the system cannot run in Auto operation mode.
To enable Auto operation mode for VRV heat pump systems, go for remote
controller setpoint logic.
Enable Setback temperature control. Setback is a function that keeps the room
temperature in a specific range when the system is turned off (by the user, the
schedule function, or the OFF timer). To achieve this, the system temporarily runs
in Heating or Cooling operation mode, according to the setback setpoint and
recovery differential.
Example:
10ºC
12ºC
Settings
Heating
Heating
operation

setback

setpoint
Heating
recovery
differential
DIFF 3°C
DIFF 5°C
OFF
33ºC
35ºC
10°C
If the room temperature drops below
10°C, the system automatically starts
heating operation. If after 30 minutes
the temperature rises above 12°C, the
+2°
system stops heating operation, and
turns off again. When the room
temperature drops below 10°C again,
the process gets repeated.
15
About the app
|
Result
Installer and user reference guide
109