Wiring For Module Fault Relay - Honeywell AlarmNet GSMBR Installation And Setup Manual

Communications module
Table of Contents

Advertisement

9
LRR / AAV
TRIGGER
8
LYNXR/LYNXR-EN
CONTROL PANEL
Figure 2-6. Wiring Zone Z1/Z2 Input for a LYNXR Trigger Output
TRANSFORMER
2K EOL
N.O.
RESISTOR
Figure 2-7. Wiring Zone Z1/Z2 Input for EOL Supervised N.O./N.C. Triggers

Wiring for Module Fault Relay

If the communications module detects a fault in its operation, it generates a fault output.
This output can be used to trigger a supervised zone in the control panel.
The communications module fault output can be programmed for fail-safe mode (see the
prompt "FLT REL ON Y/N"). In this mode, the fault output from the communications
module is energized to ground unless a fault occurs.
To sense a module's fault at the control panel, make connections as shown in Figure 2-8,
using the proper EOL resistor required by the control panel.
NOTE: A 24 hour supervisory zone may be assigned on the control panel to monitor any
communications module faults.
TRANSFORMER
TB1
2K EOL
RESISTOR
COMMUNICATIONS
MODULE
TB1
1
AC
AC
2
GND
4
N.C.
ZONE INPUT Z1/Z2
5
COMMUNICATIONS
MODULE
Section 2: Mounting and Wiring
1
AC INPUT 1
AC INPUT 2
2
4
GND
ZONE INPUT Z1/Z2
5
J1
BATTERY
J1
BATTERY
2-5